水厂深度处理触摸屏操作说明

目录

金山水厂深度处理(触摸屏)操作说明 ····················· 3

1主画面概况 ························································································ 3

1.1设备状态一览 ····································································································· 3 1.2监控系统登陆 ····································································································· 4 1.3触摸屏主画面 ····································································································· 5 2深度处理滤格 ······································································································ 5 2.1深度处理滤格主画面 ························································································· 5 2.2滤格控制画面 ····································································································· 7 2.2.1 一般阀门控制 ··························································································· 8 2.2.2可调节阀门控制 ························································································ 9 2.2.3反冲洗条件 ······························································································ 10 3提升泵系统 ········································································································· 14 3.1提升系统主画面 ······························································································· 15 3.1.1提升泵控制 ······························································································ 16 4反洗水泵系统 ···································································································· 17 4.1反洗水系统主画面 ··························································································· 17 4.1.1反冲洗水阀控制 ······················································································ 19 4.1.2反冲洗水泵控制 ······················································································ 20 5报警表格 ·············································································································· 21

金山水厂深度处理(触摸屏)操作说明

1主画面概况

金山水厂深度处理监控系统(触摸屏 ip:192.168.2.229)安装在在电气室深度处理主plc 柜上,主要监控深度处理所有工况和设备。下面是对如何操作该监控系统作一个说明。

1.1设备状态一览

图表 1-1

上图是监控系统中各个设备不同状态的说明。

1.2监控系统登陆

(1) (2)

(4) (3)

图表 1-2

为确保安全,在使用监控系统前需要用户登陆。触摸屏登陆界面如上图所示:

(1) 输入用户名

(2) 输入密码

(3) 用户名密码填写完毕后点击此键登陆

(4) 当前用户为opr 后,点击此键进入主画面

一般权限—— 用户名:none 密码:none 只能切换观测画面 操作员权限——用户名:opr 密码:opr 可以控制操作设备

注意:在输入用户名和密码时保持字母小写

1.3触摸屏主画面

图表 1-3

上图是登陆系统后的主画面,显示了整个深度处理总体流程,部分重要数据作了清楚的显示。

1. 当前日期时间

2. 其他部分画面菜单键,可以进入信息更为详细的分部画面。包括:滤格;提升泵系统 ;反洗水泵系统 ;报警表格 ;登陆界面

3. 绿色部分的高度代表了当前液位的高度,和水池上方显示的液位数据对应

4. 风机开启的数量

2深度处理滤格

2.1深度处理滤格主画面

该主画面显示了整个深度处理过滤池的工艺流程,每个滤池设备的状态和主要

数据都可一览。如下图所示:

图表 2-1

1. 1#进水阀状态

2. 2#进水阀状态

3. 排水阀状态

4. 反冲洗水阀状态

5.清水调节阀的开度和状态

6.反冲洗气阀状态

7.排气阀状态

8.表示该滤格此时的运行状态

9. 点击滤格本体将进入该滤格详细状态显示和操作画面

2.2滤格控制画面

图表 2-2

1. 远程/就地 模式状态显示;当就地时 滤格各个阀门只能通过现场plc 柜上的按钮进行操作;当远程时 滤格由plc 自动过滤程序运行,且只能在画面上操作,现场阀门手动操作无效。注:此模式的切换只能在现场plc 柜上操作。

2. 自动/手动 模式状态监控;当手动时 滤格的反冲洗由画面上开关阀门操作;当自动时 反冲洗流程将由plc 控制自动运行。注:此模式的切换只能在画面上操作。

3. 滤格运行时间 滤格自动过滤的运行累计时间。

4. 顺控复位 当出现自动过滤流程中断、停滞、故障时,可点击此按钮对自动过滤进行初始化,让自动过滤流程重置。

5. 显示当前滤格出口压力。

6. 滤格静置倒计时 显示当前滤格静置流程结束前剩余时间。静置总时间在滤格时间设定中设置。

7. 点击此按钮进入滤格自动反冲洗流程。注:当满足自动反冲洗条件方可点击此按钮否则无法操作。

8. 滤格时间设定 包括气洗流程时间设定;水洗流程时间设定;静置时间设定;过滤间隔时间设定。

9. 点击水阀弹出水阀操作面板,可以进行相关控制。

10. 点击调节阀弹出调节阀操作面板,可以进行相关控制。

11. 当滤格没有满足反自动冲洗条件时,此按钮会显示,点击后弹出自动反冲洗条件画面。

12.反洗继续 当风机启动故障导致反冲洗自动流程中断时,此按钮显示,排除故障后,点击此按钮可以继续之前的反冲洗自动流程。

13.反洗结束 当风机启动故障导致反冲洗自动流程中断时,此按钮显示,点击此按钮可以中止反冲洗自动流程。

14.风机报警复位 当风机停止故障导致反冲洗自动流程中断时,此按钮显示,点击此按钮可以复位报警。

2.2.1 一般阀门控制

图表 2-2-1

1. 手动 阀门手/自动切换;手动模式时阀门可以在面板上操作开阀关阀,此时该阀门无法投入到自动流程中。自动(默认)时面板上操作阀门无效,此时该阀门投入到自动流程中。

2. 调试 点击进入调试模式。

3. 检修 点击进入检修模式。

4. 停止 (手动模式下)点击阀门停止动作保持当前位置。

5. 开阀 (手动模式下)点击阀门开启直到开到位。

6. 关阀 (手动模式下)点击阀门关闭直到关到位。

7. 故障复位 当阀门出现故障时,点击此按钮清除故障报警。

2.2.2可调节阀门控制

图表 2-2-2

1. 手动/自动 调节阀手动/自动模式切换;手动模式下阀位开度可手动调节;自动模式下阀位开度自动随滤格液位设定值调节。

2. 阀位调节 手动模式下可用;手动输入调节阀开度。

3. 液位调节 自动模式下可用;输入滤格自动运行时需要保持的液位值,程序会自动调节阀门的开度。

4. AO 手动输入的阀门开度值棒图。

5. AI 调节阀当前开度值棒图。

6. SP 自动调节滤格液位设定值棒图。

7. PV 滤格当前液位值棒图。 2.2.3反冲洗条件

图表 2-2-3-1

当满足反冲洗条件时,点击反冲洗按钮会弹出确认对话框 如上图所示

1. 自动反冲洗确认 点击确认开始自动反冲洗流程。

2. 取消自动反冲洗 点击取消自动反冲洗流程。

当不满足反冲洗条件时,如下图所示

图表

2-2-3-2

1. 当自动反冲洗条件不满足时,反冲洗按钮为无效状态。

2. 当自动反冲洗条件不满足时,反洗条件按钮显示,点击后出现如下图所示条件诊断画面。

图表 2-2-3-3

1.1#滤格准备条件 该窗口罗列了所有自动反洗前需要满足的条件。

2.条件判断 条件前为绿灯表示该条件满足,为黑灯表示条件不满足。

3. 二级条件 条件下有横线表示该条件还有二级条件,只有该条件的所有二级条件满足了该条件才能满足。点击后弹出对应二级条件(4)。

4. 对应上级条件(3)的二级条件窗口。只有该窗口所有条件满足了,上级条件才能满足。

上图显示滤格准备条件和阀门准备好二级条件。

图表 2-2-3-4

1. 滤格反洗允许条件

2. 滤格反洗允许二级条件 4个滤格一组,当其他3个滤格中有两个正在投运或运行中,则该滤格反洗允许条件满足。

图表 2-2-3-5

1. 反冲洗水泵准备好

2. 反冲洗水泵准备好二级条件

3. 反冲洗水泵三台可用二级条件 4个水泵都允许顺控那么该条件满足

图表 2-2-3-6

1. 反洗泵顺控允许的二级条件 当反洗水泵的所有条件都满足后,此反洗水泵顺控允许条件就满足,当4个反洗泵顺控都允许后,反洗水泵三台可用条件满足。

3提升泵系统

提升泵系统是给臭氧接触池供水的重要环节,滤格的过滤用的臭氧水就是先通过提升泵系统提升清水池的水到臭氧接触池产生的。

以下是提升泵系统的说明。

3.1提升系统主画面

图表 3-1

1. 2. 3. 4.

吸水井的液位高度 提升泵给臭氧接触池的流量 提升泵频率输出百分比 点击提升泵进入

3.1.1提升泵控制

图表 3-1-1

1. 液位手动/自动 液位手动/自动模式切换;手动模式下泵的频率可手动调节;自动模式下泵的频率自动随吸水井液位设定值调节。

2. 提升泵手动/自动 提升泵手动/自动模式切换;手动模式时提升泵可以在面板上操作启动停止,此时该提升泵无法投入到自动流程中。自动(默认)时面板上操作泵无效,此时该泵投入到自动流程中。

3. 调试 点击进入调试模式。

4. 检修 点击进入检修模式。

5. 频率调节 手动模式下可用;手动输入泵电机频率。

6. 液位设定 自动模式下可用;输入吸水井自动运行时需要保持的液位值,程序会自动调节泵的频率。

7. 启动 手动模式下点击启动提升泵

8. 停止 手动模式下点击停止提升泵

9. 故障复位 点击复位提升泵故障报警

10. AO 手动输入的泵频率值棒图。

11. AI 当前泵频率值棒图。

12. SP 自动调节吸水井液位设定值棒图。

13. PV 滤格当前吸水井液位值棒图。

4反洗水泵系统

反洗水系统是给滤格反洗流程供水的重要环节,滤格需要反洗时,反洗水泵和阀门要配合打开,维持一定流量达到反洗目的。

以下是提升泵系统的说明。 4.1反洗水系统主画面

图表 4-1

1. 反冲洗步启步停状态 显示反冲洗自动步启和自动步停的实时状态

2. 步启步停控制 反冲洗自动步启 点击自动按顺序启动阀门和反冲洗水泵;

反冲洗自动步停 点击自动按顺序停止阀门和反冲洗水泵; 注:在远程状态下才能控制

3. 顺控复位 当反冲洗顺控因故障出现中断或停滞时,点击该按钮初始化顺控,

重置程序。

4. 反冲洗水池液位高度

5. 反冲洗水泵出水压力

6. 反冲洗水阀状态 点击反冲洗水阀弹出

7. 反冲洗水泵状态 点击反冲洗水泵弹出

8. 反冲洗水泵当前频率

9. 液位手动/自动 液位手动/自动模式切换;手动模式下各反洗水泵手动启停; 自动模式下各反洗水泵自动启停并随反冲水系统出水流量设定值调节输出频率。

10. SP 反洗水流量自动控制流量设定值棒图

11. PV 当前反洗水系统出水流量值棒图

12. 当前反洗水系统出水流量值

图表 4-1-1

1. 手动 阀门手/自动切换;手动模式时阀门可以在面板上操作开阀关阀,此时该阀门无法投入到自动流程中。自动(默认)时面板上操作阀门无效,此时该阀门投入到自动流程中。

2. 调试 点击进入调试模式。

3. 检修 点击进入检修模式。

4. 停止 (手动模式下)点击阀门停止动作保持当前位置。

5. 开阀 (手动模式下)点击阀门开启直到开到位。

6. 关阀 (手动模式下)点击阀门关闭直到关到位。

7. 故障复位 当阀门出现故障时,点击此按钮清除故障报警。

图表 4-1-2

1. 反洗水泵手动/自动 反洗水泵手动/自动模式切换;手动模式时反洗水泵可以在面板上操作启动停止以及调节泵电机频率,此时该反洗水泵无法投入到自动流程中。自动(默认)时面板上操作泵无效,此时该泵投入到自动流程中。

2. 调试 点击进入调试模式。

3. 检修 点击进入检修模式。

4. 启动 手动模式下点击启动反洗水泵

5. 停止 手动模式下点击停止反洗水泵

6. 故障复位 点击复位反洗水泵故障报警

7. 频率调节 手动模式下可用;手动输入泵电机频率。

8. AO 手动输入的泵频率值棒图。

9. AI 当前泵频率值棒图。

镇江金山水厂深度处理

5报警表格

图表 5

1. 故障报警信息栏 信息包括日期、时间、报警信息

2. 确认所有报警

3. 确认选中报警

2012-10-29 编辑:胡飞

目录

金山水厂深度处理(触摸屏)操作说明 ····················· 3

1主画面概况 ························································································ 3

1.1设备状态一览 ····································································································· 3 1.2监控系统登陆 ····································································································· 4 1.3触摸屏主画面 ····································································································· 5 2深度处理滤格 ······································································································ 5 2.1深度处理滤格主画面 ························································································· 5 2.2滤格控制画面 ····································································································· 7 2.2.1 一般阀门控制 ··························································································· 8 2.2.2可调节阀门控制 ························································································ 9 2.2.3反冲洗条件 ······························································································ 10 3提升泵系统 ········································································································· 14 3.1提升系统主画面 ······························································································· 15 3.1.1提升泵控制 ······························································································ 16 4反洗水泵系统 ···································································································· 17 4.1反洗水系统主画面 ··························································································· 17 4.1.1反冲洗水阀控制 ······················································································ 19 4.1.2反冲洗水泵控制 ······················································································ 20 5报警表格 ·············································································································· 21

金山水厂深度处理(触摸屏)操作说明

1主画面概况

金山水厂深度处理监控系统(触摸屏 ip:192.168.2.229)安装在在电气室深度处理主plc 柜上,主要监控深度处理所有工况和设备。下面是对如何操作该监控系统作一个说明。

1.1设备状态一览

图表 1-1

上图是监控系统中各个设备不同状态的说明。

1.2监控系统登陆

(1) (2)

(4) (3)

图表 1-2

为确保安全,在使用监控系统前需要用户登陆。触摸屏登陆界面如上图所示:

(1) 输入用户名

(2) 输入密码

(3) 用户名密码填写完毕后点击此键登陆

(4) 当前用户为opr 后,点击此键进入主画面

一般权限—— 用户名:none 密码:none 只能切换观测画面 操作员权限——用户名:opr 密码:opr 可以控制操作设备

注意:在输入用户名和密码时保持字母小写

1.3触摸屏主画面

图表 1-3

上图是登陆系统后的主画面,显示了整个深度处理总体流程,部分重要数据作了清楚的显示。

1. 当前日期时间

2. 其他部分画面菜单键,可以进入信息更为详细的分部画面。包括:滤格;提升泵系统 ;反洗水泵系统 ;报警表格 ;登陆界面

3. 绿色部分的高度代表了当前液位的高度,和水池上方显示的液位数据对应

4. 风机开启的数量

2深度处理滤格

2.1深度处理滤格主画面

该主画面显示了整个深度处理过滤池的工艺流程,每个滤池设备的状态和主要

数据都可一览。如下图所示:

图表 2-1

1. 1#进水阀状态

2. 2#进水阀状态

3. 排水阀状态

4. 反冲洗水阀状态

5.清水调节阀的开度和状态

6.反冲洗气阀状态

7.排气阀状态

8.表示该滤格此时的运行状态

9. 点击滤格本体将进入该滤格详细状态显示和操作画面

2.2滤格控制画面

图表 2-2

1. 远程/就地 模式状态显示;当就地时 滤格各个阀门只能通过现场plc 柜上的按钮进行操作;当远程时 滤格由plc 自动过滤程序运行,且只能在画面上操作,现场阀门手动操作无效。注:此模式的切换只能在现场plc 柜上操作。

2. 自动/手动 模式状态监控;当手动时 滤格的反冲洗由画面上开关阀门操作;当自动时 反冲洗流程将由plc 控制自动运行。注:此模式的切换只能在画面上操作。

3. 滤格运行时间 滤格自动过滤的运行累计时间。

4. 顺控复位 当出现自动过滤流程中断、停滞、故障时,可点击此按钮对自动过滤进行初始化,让自动过滤流程重置。

5. 显示当前滤格出口压力。

6. 滤格静置倒计时 显示当前滤格静置流程结束前剩余时间。静置总时间在滤格时间设定中设置。

7. 点击此按钮进入滤格自动反冲洗流程。注:当满足自动反冲洗条件方可点击此按钮否则无法操作。

8. 滤格时间设定 包括气洗流程时间设定;水洗流程时间设定;静置时间设定;过滤间隔时间设定。

9. 点击水阀弹出水阀操作面板,可以进行相关控制。

10. 点击调节阀弹出调节阀操作面板,可以进行相关控制。

11. 当滤格没有满足反自动冲洗条件时,此按钮会显示,点击后弹出自动反冲洗条件画面。

12.反洗继续 当风机启动故障导致反冲洗自动流程中断时,此按钮显示,排除故障后,点击此按钮可以继续之前的反冲洗自动流程。

13.反洗结束 当风机启动故障导致反冲洗自动流程中断时,此按钮显示,点击此按钮可以中止反冲洗自动流程。

14.风机报警复位 当风机停止故障导致反冲洗自动流程中断时,此按钮显示,点击此按钮可以复位报警。

2.2.1 一般阀门控制

图表 2-2-1

1. 手动 阀门手/自动切换;手动模式时阀门可以在面板上操作开阀关阀,此时该阀门无法投入到自动流程中。自动(默认)时面板上操作阀门无效,此时该阀门投入到自动流程中。

2. 调试 点击进入调试模式。

3. 检修 点击进入检修模式。

4. 停止 (手动模式下)点击阀门停止动作保持当前位置。

5. 开阀 (手动模式下)点击阀门开启直到开到位。

6. 关阀 (手动模式下)点击阀门关闭直到关到位。

7. 故障复位 当阀门出现故障时,点击此按钮清除故障报警。

2.2.2可调节阀门控制

图表 2-2-2

1. 手动/自动 调节阀手动/自动模式切换;手动模式下阀位开度可手动调节;自动模式下阀位开度自动随滤格液位设定值调节。

2. 阀位调节 手动模式下可用;手动输入调节阀开度。

3. 液位调节 自动模式下可用;输入滤格自动运行时需要保持的液位值,程序会自动调节阀门的开度。

4. AO 手动输入的阀门开度值棒图。

5. AI 调节阀当前开度值棒图。

6. SP 自动调节滤格液位设定值棒图。

7. PV 滤格当前液位值棒图。 2.2.3反冲洗条件

图表 2-2-3-1

当满足反冲洗条件时,点击反冲洗按钮会弹出确认对话框 如上图所示

1. 自动反冲洗确认 点击确认开始自动反冲洗流程。

2. 取消自动反冲洗 点击取消自动反冲洗流程。

当不满足反冲洗条件时,如下图所示

图表

2-2-3-2

1. 当自动反冲洗条件不满足时,反冲洗按钮为无效状态。

2. 当自动反冲洗条件不满足时,反洗条件按钮显示,点击后出现如下图所示条件诊断画面。

图表 2-2-3-3

1.1#滤格准备条件 该窗口罗列了所有自动反洗前需要满足的条件。

2.条件判断 条件前为绿灯表示该条件满足,为黑灯表示条件不满足。

3. 二级条件 条件下有横线表示该条件还有二级条件,只有该条件的所有二级条件满足了该条件才能满足。点击后弹出对应二级条件(4)。

4. 对应上级条件(3)的二级条件窗口。只有该窗口所有条件满足了,上级条件才能满足。

上图显示滤格准备条件和阀门准备好二级条件。

图表 2-2-3-4

1. 滤格反洗允许条件

2. 滤格反洗允许二级条件 4个滤格一组,当其他3个滤格中有两个正在投运或运行中,则该滤格反洗允许条件满足。

图表 2-2-3-5

1. 反冲洗水泵准备好

2. 反冲洗水泵准备好二级条件

3. 反冲洗水泵三台可用二级条件 4个水泵都允许顺控那么该条件满足

图表 2-2-3-6

1. 反洗泵顺控允许的二级条件 当反洗水泵的所有条件都满足后,此反洗水泵顺控允许条件就满足,当4个反洗泵顺控都允许后,反洗水泵三台可用条件满足。

3提升泵系统

提升泵系统是给臭氧接触池供水的重要环节,滤格的过滤用的臭氧水就是先通过提升泵系统提升清水池的水到臭氧接触池产生的。

以下是提升泵系统的说明。

3.1提升系统主画面

图表 3-1

1. 2. 3. 4.

吸水井的液位高度 提升泵给臭氧接触池的流量 提升泵频率输出百分比 点击提升泵进入

3.1.1提升泵控制

图表 3-1-1

1. 液位手动/自动 液位手动/自动模式切换;手动模式下泵的频率可手动调节;自动模式下泵的频率自动随吸水井液位设定值调节。

2. 提升泵手动/自动 提升泵手动/自动模式切换;手动模式时提升泵可以在面板上操作启动停止,此时该提升泵无法投入到自动流程中。自动(默认)时面板上操作泵无效,此时该泵投入到自动流程中。

3. 调试 点击进入调试模式。

4. 检修 点击进入检修模式。

5. 频率调节 手动模式下可用;手动输入泵电机频率。

6. 液位设定 自动模式下可用;输入吸水井自动运行时需要保持的液位值,程序会自动调节泵的频率。

7. 启动 手动模式下点击启动提升泵

8. 停止 手动模式下点击停止提升泵

9. 故障复位 点击复位提升泵故障报警

10. AO 手动输入的泵频率值棒图。

11. AI 当前泵频率值棒图。

12. SP 自动调节吸水井液位设定值棒图。

13. PV 滤格当前吸水井液位值棒图。

4反洗水泵系统

反洗水系统是给滤格反洗流程供水的重要环节,滤格需要反洗时,反洗水泵和阀门要配合打开,维持一定流量达到反洗目的。

以下是提升泵系统的说明。 4.1反洗水系统主画面

图表 4-1

1. 反冲洗步启步停状态 显示反冲洗自动步启和自动步停的实时状态

2. 步启步停控制 反冲洗自动步启 点击自动按顺序启动阀门和反冲洗水泵;

反冲洗自动步停 点击自动按顺序停止阀门和反冲洗水泵; 注:在远程状态下才能控制

3. 顺控复位 当反冲洗顺控因故障出现中断或停滞时,点击该按钮初始化顺控,

重置程序。

4. 反冲洗水池液位高度

5. 反冲洗水泵出水压力

6. 反冲洗水阀状态 点击反冲洗水阀弹出

7. 反冲洗水泵状态 点击反冲洗水泵弹出

8. 反冲洗水泵当前频率

9. 液位手动/自动 液位手动/自动模式切换;手动模式下各反洗水泵手动启停; 自动模式下各反洗水泵自动启停并随反冲水系统出水流量设定值调节输出频率。

10. SP 反洗水流量自动控制流量设定值棒图

11. PV 当前反洗水系统出水流量值棒图

12. 当前反洗水系统出水流量值

图表 4-1-1

1. 手动 阀门手/自动切换;手动模式时阀门可以在面板上操作开阀关阀,此时该阀门无法投入到自动流程中。自动(默认)时面板上操作阀门无效,此时该阀门投入到自动流程中。

2. 调试 点击进入调试模式。

3. 检修 点击进入检修模式。

4. 停止 (手动模式下)点击阀门停止动作保持当前位置。

5. 开阀 (手动模式下)点击阀门开启直到开到位。

6. 关阀 (手动模式下)点击阀门关闭直到关到位。

7. 故障复位 当阀门出现故障时,点击此按钮清除故障报警。

图表 4-1-2

1. 反洗水泵手动/自动 反洗水泵手动/自动模式切换;手动模式时反洗水泵可以在面板上操作启动停止以及调节泵电机频率,此时该反洗水泵无法投入到自动流程中。自动(默认)时面板上操作泵无效,此时该泵投入到自动流程中。

2. 调试 点击进入调试模式。

3. 检修 点击进入检修模式。

4. 启动 手动模式下点击启动反洗水泵

5. 停止 手动模式下点击停止反洗水泵

6. 故障复位 点击复位反洗水泵故障报警

7. 频率调节 手动模式下可用;手动输入泵电机频率。

8. AO 手动输入的泵频率值棒图。

9. AI 当前泵频率值棒图。

镇江金山水厂深度处理

5报警表格

图表 5

1. 故障报警信息栏 信息包括日期、时间、报警信息

2. 确认所有报警

3. 确认选中报警

2012-10-29 编辑:胡飞


相关内容

  • 净水厂开题报告
  • 毕业设计(论文) 开 题 报 告 题 目 A市净水厂工艺设计 专 业 环境工程 班 级 环境121 学 生 王鸣 指导教师 万甜 一.毕业设计(论文)课题来源.类型 地面标高为24.5m),地势平坦.水源取水口位于水厂西北方向10km,水源所在河流的最高水位为19.9m,最低水位为18.6m,水源至 ...

  • 污水处理厂设计和运行中的节能考虑
  • 聚焦城镇污水处理行业的节能减排 污水处理厂设计和运行中的 节能考虑 文 / 李春光 徐晓宇 (上海市政工程设计研究总院 上海 200092) 一.前言 随着国家环境保护政策的推进,近几年以及今后的一段时间城市污水处理设施的投资和建设规模不断增长,污水处理率以及处理程度也不断提高,导致了污水处理厂运行 ...

  • 大庆市东城水厂水处理工艺流程剖析
  • 2011年第1期 (第39卷) Heilongjiang 黑龙江水利科技 ScienceandTechnologyof No.1.20ll WaterConservancy(TodalNo.39) 文章编号:1007-7596(201I)01-0093-02 大庆市东城水厂水处理工艺流程剖析 曹清海 ...

  • 基于静沉试验的给水厂污泥重力浓缩池的设计探讨_谢敏
  • DOI 牶牨牥牣牨牫牱牳牴牤j 牣cn ki 牣w we 牨牴牰牬牣牪牥牥牰牣牨牪牣牥牥牨 城市给排水 基于静沉试验的给水厂污泥重力浓缩池的设计探讨 谢 敏 施 周 李冬梅 李淑展 邓 军 (湖南大学土木工程学院水工程与科学系, 长沙 410082) 摘要 根据实测得到的静态沉降曲线讨论迪克理论和柯 ...

  • 水厂预处理及深度处理的几点研究
  • 龙源期刊网 http://www.qikan.com.cn 水厂预处理及深度处理的几点研究 作者:任山 来源:<价值工程>2014年第16期 摘要: 近年来,企业造成的水源污染现象不断增多,阻碍我国持续健康的发展.随着经济的发展,我国的水厂已经探索出多种多样的处理技术,从而确保水源的优质 ...

  • 自来水厂不同水处理工艺各单元水有机物致突变性变化规律
  • 环境与健康杂志2010年7月第27卷第7期JEnvironHealth,July2010,Vol.27,No.7 ·587· [论著] 文章编号:1001-5914(2010)07-0587-04 自来水厂不同水处理工艺各单元水有机物致突变性变化规律 余淑苑1,张振1,张隽2,周国洪1,李思果1,吴 ...

  • 污水厂课程设计要求和步骤
  • 污水厂课程设计大纲 根据所给条件,应用所学的各种污水处理技术和方法,根据水质指标和出水标准,进行污水处理厂设计.说明计算书中确定污水处理方案,说明污水处理厂的位置.占地面积.处理能力,处理标准和方法:按流程说明各构筑物的的功能及类型.主要设计参数.尺寸大小.所需设备类型.台数和技术性能:对厂区平面和 ...

  • 活性炭吸附池工艺设计的探讨
  • 活性炭吸附池工艺设计的探讨 1 深圳市笔架山水厂活性炭吸附池工艺设计概况 深圳市笔架山水厂扩(改)建工程于1999年开始方案设计,2003年被确定为国家"863"课题"南方地区安全饮用水保障技术"的示范工程(以下简称示范工程),水厂扩建工程规模20万m3/d, ...

  • 关于自来水厂生产废水的回用
  • 关于自来水厂生产废水的回用 许嘉炯 郑志民 许建华 (上海市政工程设计研究院 200092) (同济大学环境科学与工程学院 200092) 摘要:本文主要针对自来水厂生产废水的回用问题进行了探讨,对直接回用和处理回用两种回用过程中所产生的水质问题进行了分析:针对不同的水质问题提出了处理方式:对于回用 ...