轨道交通 供电系统

毕业设计文件

设计题目: 城市轨道交通供电系统概述与分析———— 专业:

指导教师:

摘要:

近几年来,随着我国大城市交通压力的逐渐增大,城市轨道交通系统的发展步伐亦逐日加快。本文主要介绍了城市轨道交通供电系统的构成以及详细介绍了各部分的功能及分类,总结了国内外各城市地铁供电系统的应用方式。

因本人专业偏向于弱电,所以本文在全面总结城市轨道供电系统的前提下,着重介绍了变电所内的二次设备,从设备的种类、分类、用途以及构造方面加以了解。同时以沈阳地铁为案例介绍、分析了此轨道交通供电系统方案。

关键词:轨道交通 供电系统 二次设备 Abstract :

In recent years, with the city traffic pressure increase gradually, the development of urban rail transit system is accelerated pace of daily. This paper mainly introduces the power supply system of urban rail transit are introduced in detail the composition and function of each part and classification, summarizes the domestic and international every city metro power system application.

Because I am in favour of professional, so this weak in comprehensive summary of urban rail power supply system, emphatically introduces the condition of equipment, within the substation equipment types, from classification, applications and structural aspects. In case of shenyang subway is introduced and analyzed the rail traffic system.

Key words: Rail transit Power supply system Second equipment

目录

1城市轨道交通供电系统构成 ................................. 8 1.1地铁供电系统的组成 ..................................... 8 1.2牵引电力制式 .......................................... 10 2变电所的主要电气设备 .................................... 12 2.1变电所的分类 .......................................... 12 2.2变压器的工作原理、分类及结构 .......................... 13 2.2.1变压器的工作原理 .................................... 13 2.2.2变压器的分类及结构 .................................. 13 2.2.3变压器型号与额定值意义 .............................. 14 2.4变电所内的开关设备 .................................... 15 2.4.1高压断路器 .......................................... 15 2.4.2隔离开关 ............................................ 15 2.4.3负荷开关 ............................................ 16 2.4.4互感器 .............................................. 16 2.5变电所内的保护设备 .................................... 17

2.5.1熔断器 .............................................. 17 2.5.2变配电所的防雷措施 .................................. 17 2.6补偿设备 .............................................. 18 2.7成套设备 .............................................. 18 2.8电力保护系统 .......................................... 18 3电气主接线 .............................................. 20 3.1电气主接线基本要求 .................................... 20 3.2主接线的基本接线方式 .................................. 20 3.2.1单母线不分段 ........................................ 20 3.2.2单母线分段 .......................................... 21 3.2.3单母线带旁路接线 .................................... 22 3.2.4双母线接线 .......................................... 22 3.2.5桥式接线 ............................................ 22 3.3沈阳地铁采用的主接线方案 .............................. 23 4牵引网 .................................................. 24 4.1牵引网与接触网 ........................................ 24

4.2接触网的工作特点 ...................................... 24 4.3对接触网的基本要求 .................................... 25 4.4接触网的分类及其特点 .................................. 25 4.4.1接触轨式馈电方式的特点 .............................. 25 4.4.2接触网馈电方式的特点 ................................ 26 5电力监控 ................................................ 29 5.1电力监控系统概述 ...................................... 29 5.2沈阳地铁电力监控系统 .................................. 29 结束语 . ................................................... 31 【参考文献】 . ............................................. 32

城市轨道交通供电系统概述及分析

前言

世界上地铁交通很早就作为公共交通在城市中出现。随着科学技术和城市化的发展,大运量的地铁交通在现代大城市中越来越起着重要的作用。经济发达国家城市的交通发展历史告诉我们,只有采用大客运量的地铁交通系统,才是从根本上改善城市公共交通状况的有效途径。

我国发展地铁交通的历史也并不短,40年前北京就开始了地铁建设。想建地铁的城市也不少, 但一直因造价太贵而却步。至今一些百万人口以上的大城市, 仍然用传统的公共汽车和无轨电车来维持客运的做法, 已越来越不能满足城市居民高频率出行的需要。因而目前很多大城市又在考虑和策划修建地铁交通项目,除北京外, 上海﹑广州等城市也有地铁线路在运营, 但远不能较为普遍地满足需要。由于我国城市地铁交通的应用技术和基础理论都还处于开拓阶段, 项目实施的大多数情况是要引进技术和设备, 国产化率低, 成为工程造价昂贵的主要原因。因而提高我国城市地铁交通行业的技术力量, 发挥自主建设能力, 努力降低工程价, 已是健康发展大运量地铁交通的关键。

电力牵引供电系统是城市轨道交通的重要组成部分, 没有电力牵引供电系统的可靠安全供电, 就不可能有城市轨道交通的正常运行。为此, 本文对电力牵引供电系统的特点作了深入的分析和研究。

1城市轨道交通供电系统构成

通常国家供电系统总是把在同一区域(或大区)的许多发电厂通过高压输电线和变电所连接起来成为一个大的统一的供电系统,向该区域的负荷供电,这样由各级电压输电线将发电厂、变电所和电力用户联接起来的一个发电、输电、变电、配电和用户的统一体称为电力系统。

地铁用电取自城市电网,经过地铁供电系统实现输送和变换,应适当的电压等级共给地铁各类设备,例如电力机车、照明、通风、空调、排水、自动扶梯、自动检票机等用电设备。

1.1地铁供电系统的组成

城市轨道交通系统的组成包括牵引供电系统和动力照明供电系统,如图1.1所示:

图1.1 城市轨道交通规定系统组成

城市轨道交通系统是一级电力负荷,安全、可靠是供电系统的主要目的。在地铁供电系统中,牵引供电系统由于直接给列车提供动力,占据着举足轻重的地位。该系统的好坏直接影响整个地铁供电系统质量的高低。如果该系统出现问题,小则影响某个变电站、几个供电区间的输送电,大则引起整个牵引供电系统

的崩溃,给地铁列车的正常运营造成影响,因此要保证安全可靠的供电需要采用两路独立电源供电和增设应急电源。

在城市轨道交通供电系统中,从发电厂经升压、高压输电网、区域变电站至主降压变电站部分通常被称为牵引供电系统的“外部(或一次)供电系统”。

从主降压变电所(当它不属于电力部门时)及其以后部分统称为“牵引供电系统”。它应该包括:主变电所、直流牵引变电所、馈电线、接触网、走行轨及回流线等。直流牵引变电所将三相高压交流电变成适合电动车辆应用的低压直流电。馈电线是将牵引变电所的直流电送到接触网上。接触网是沿列车走行轨架设的特殊供电线路,电动车辆通过其受流器与接触网的直接接触而获得电力。走形轨道构成牵引供电回路的一部分。回流线将轨道回流引向牵引变电所。

牵引供电系统组成包括以下几个方面,如图1.2所示:

图1.2牵引供电系统组成

城市轨道交通供电系统负荷可分为一级重要负荷和二级、三级负荷,其中一级重要负荷包括防灾报警、事故照明、通信信号、通风消防,对于一级重要负荷若中断供电将可能发生中毒、爆炸和火灾危险,因此须保证两路独立电源供电,并备有应急电源,而其他用电设备,例如电梯、一般照明、普通风机、排污泵等则属于二级、三级负荷。

在正常情况下,变电所同时向各个负荷供电,如若供电系统发生故障或者出现事故时,则断开二、三级负荷,优先向一级负荷供电,以最大限度地保证地铁安全。

如图1.3所示:

图1.3 400V低压系统简图

1.2牵引电力制式

在城市轨道交通中电力机车必须能产生足够大的牵引力,具有较高的过载能力,并能充分利用牵引电机容量,容易实现调速以及先进的经济技术指标的特点,常采用直流电机和交流电机两大类,同时各有优缺点。

对于直流电机来说,启动和调速容易实现,但电机结构复杂、成本高,且接通电源瞬间启动电流太大,串联大功率电阻限流和降压使能量损耗大,北京一号线采用直流电机。

而交流电机性价比高于直流电机,寿命长,几乎免于维护,特别是调压调频逆变器系统使启动和调速更容易实现,较为普遍使用。

在城市轨道交通的牵引制式中 ,直流制比同电压交流制供电的电压损失

小,且地铁适于电压较低的供电电压,因此城市交通通常采用低电压的直流供电制式,国际拟定标准有600 V、750V ,我国国标为750V 、1500V ;北京、天津采用DC750 V牵引制式,电压波动范围为DC500V ~DC900V ,上海、广州、沈阳等采用DC1500V 牵引制式,电压波动范围为DC1000V ~DC1800V 。

沈阳地铁牵引系统受电方式是牵引系统通过受电弓从DC1500V 接触网受电,每列车配备两台DC110V 电动气泵,升弓时间不大于8秒,降弓时间不大于7秒,沈阳地铁采用日本三菱交流异步电动机牵引,且采用1C4M 供电方式,即由一台牵引逆变器向四台并联电机提供变频变压三相电源,从而驱动机车。

2变电所的主要电气设备

变电所是用以实现切断或接通、改变或者调整电压的功能。

变电所内的电气设备按所属电路性质分为两大类:一次高压电路中所有的电气设备,即为一次设备;二次控制、信号和测量电路中的所有电气设备即为二次设备。

一次设备按其在一次电路中的功用又可分为变换设备、控制设备、保护设

备、补偿设备和成套设备等类型。

(1) 变换设备

用以变换电能电压或电流的设备。如电力变压器、整流器、电压互感器、电

(2)控制设备

用以控制电路通断的设备。如各种高低压开关设备。

(3)保护设备

用以保护电路过电流或过电压的设备。如高低压熔断器和避雷器等。

(4)补偿设备

用以补偿电路的无功功率以提高系统功率因数的设备。如高低压电容器、静止无功补偿设备等。

(5)成套设备

按一定的线路方案将有关一次、二次设备组合而成的设备。 如高压开关

柜,低压配电屏,高低压电容柜和成套变电站等。 流互感器等 。

2.1变电所的分类

变电所是供配电系统的核心,在供电系统中占有特别重要的地位。在城市轨道交通供电系统中,变电所可分为主变电所,牵引变电所,降压变电所

交流牵引变电所又分为工频交流牵引变电所和低频交流牵引变电所,工频交流牵引变电所是将电网电压经变压器降为25~50KV 交流电压供给电力机车,而低频交流牵引变电所经降压变频换为162/3Hz低频交流电压。对于直流牵引变电所是将电网电压经降压整流为相应等级的直流电供给城市轨道交通系统中的电力机车,其中整流是区别于交流牵引变电所最关键设备。降压整流为直流电的直流牵引变电所和车站区间供电的降压变电所合并为牵引降压变电所。

沈阳地铁一号线一期及延长线设置两座66KV/35 KV主变电所:重工街、三经街;每座主变电所由地区变电所引入两回路互相独立的6 6KV电源,变换为35 KV 输出。

设置十座牵引降压变电所:车辆段混合所、十三号街、黎明文化宫等;牵引降压变电所将输入的AC35 KV电压变换为AC1500V 和DC400 V,分别供给牵引网和动力照明配电系统。

设置降压变电所十三座:中央大街、沈阳站、青年大街等,降压变电所将输入的AC35 KV电压变换为DC400 v,供给动力照明配电系统。

另外在车辆段和控制中心设置两座跟随市降压变电所,将输入的AC35 KV电压变换为DC400 v,供给动力照明配电系统及控制系统。

2.2变压器的工作原理、分类及结构

变压器是一种静止的电器,它通过线圈间的电磁感应作用,把一种电压的电能转换为同频率的另一种电压的电能,故称变压器。实际上,它在变压的同时还能改变电流,还可改变阻抗和相数。

2.2.1变压器的工作原理

变压器的主要部件是一个铁心和套在铁心上的两个绕组,如图2.1所示。

图2.1 变压器构成简图

理想状况如下(不计电阻、铁耗和漏磁),原绕组加电压 U1 ,产生电流 I1 ,建立磁通ø ,沿铁心闭合,分别在原副绕组中感应电动势e1 和 e2 。

2.2.2变压器的分类及结构

按用途分:电力变压器和特种变压器。

按绕组数目分:单绕组(自耦)变压器、双绕组变压器、三绕组变压器和多绕组变压器。

按相数分:单相变压器、三相变压器和多相变压器。

按铁心结构分:心式变压器和壳式变压器。

按冷却介质和冷却方式分:干式变压器、油浸式变压器和充气式变压器 图2.2为油浸式变压器:

图2.2 油浸式变压器

(1)铁心

作用:变压器的主磁路;

材料:为了提高导磁性能和减少铁损,用0.35mm 厚、表面涂有绝缘漆的硅钢片叠成;基本形式:心式和壳式。

(2)绕组

变压器的一次绕组和二次绕组一般用绝缘铜线或铝线绕制而成圆筒形的多层线圈,放在铁芯柱上,导体外面采用绝缘处理。 基本形式:同心式和交叠式 。

(3)油箱及其附件

油箱、储油柜、散热器、分接开关、套管、气体继电器等。

油箱:油浸式变压器的器身浸在变压器油的油箱中。油是冷却介质,又是绝缘介质。油箱侧壁有冷却用的管子(散热器或冷却器)。

绝缘套管将线圈的高、低压引线引到箱外,是引线对地的绝缘,担负着固定的作用。

2.2.3变压器型号与额定值意义

型号表示一台变压器的结构、额定容量、电压等级、冷却方式等内容,表示方法为如图2.3:

图2.3变压器型号与额定值意义

在现代电力系统中,常采用多台变压器并联运行的方式。并联运行是将几台变压器的原、副绕组分别接到公共的母线上共同对负载供电的运行方式。变压器并联运行的条件为一次二次额定电压必须对应相等,且连接组别和短路电压须相同,以及容量尽量相同或相近。

在沈阳地铁供电系统中,各主变电所配有两台主变变压器(并联运行),三相油浸自冷双线圈有载调压降压电力变压器,型号为SZ11-31500KVA/66KV,即一次电压66KV ,容量31500KVA ;动力变压器采用AC35/0.4KV、额定功率为

1000KVA 、2000KVA 、1600KVA 的户内干式风冷式变压器;在各牵引降压混合所设置两台牵引整流变压器,采用ZQSC9-2200/35的包封式环氧树脂浇注绝缘结构干式变压器。

2.4变电所内的开关设备

2.4.1高压断路器

断路器又叫高压开关,它是变电所的重要设备之一。断路器不仅可以切断与闭合高压电路的空载电流和负载电流,而且,当系统发生故障时,它与保护装置、自动装置相配合,可以迅速地切断故障电流,以减少停电范围,防止事故扩大,保证系统的安全运行。

断路器的主要结构大体分为倒流部分、灭弧部分、绝缘部分和操作机构部分。断路器在闭合时起接通回路的作用,当断路器断开时,触头虽已分开,但触头间仍会产生电弧,因而断路器应具有灭弧能力。断路器的灭弧方式有多种,从灭弧方式上可以将断路器分为:油断路器、六氟化流断路器、真空断路器等。

2.4.2隔离开关

隔离开关是没有灭弧装置的开关电器,在分闸状态下有明显的断口,在合闸状态下能可靠的通过额定电流和短路电流。因隔离开关没有灭弧装置,不能切断负荷电流和短路电流,因此隔离开关通常和断路器配合使用,且在操作中必须注意与断路器操作的先后顺序。当合闸时,先合隔离开关,后合断路器;分闸时,先分断路器,后分隔离开关。这种操作通常称为倒闸操作。为了保证安全,一般采用连锁装置,以防止误操作。

隔离开关的主要用途有:

(1)为设备或线路的检修和分段进行电气隔离;

(2)在断口两段电位接近相等的情况下,倒换母线,改变接线方式;

(3)分合一定长度的母线和电缆;

(4)分合一定容量的空载变压器,一定长度的空载线路和电压互感器。

2.4.3负荷开关

负荷开关是在高压隔离开关的基础上加入简单的灭弧装置而成的,能切、合负荷电流,但不能切断短路电流。因此,负荷开关必须与高压断路器配合使用,短路电流由熔断器切断,而它专门在高压装置中通断负荷电流,也能在过负荷的情况下自动跳闸。

负荷开关常在一些经常需要进行分、合闸的地方使用。负荷开关的结构与断路器相似,制式开断性能要求比断路器低。因此,构造比断路器简单,操作机构动力较小,价格也较断路器低。

除了以上开关设备外,变电所内常用的还有低压刀开关、低压刀熔开关、低压断路器、直流开关等开关设备。

2.4.4互感器

互感器是一种特殊变压器,有电压互感器和电流互感器,其主要功能有变换、隔离保护功能,以及扩大仪表、继电器等二次设备应用范围。

(1)电压互感器

电压互感器的功能是将高电压变为低电压进行测量、控制。其结构特点是原绕组匝数很多,副绕组匝数很少,相当于特殊的降压变压器。工作时二次侧接电压表、继电器等,一般为100V ,相当于开路。

互感器的电压比有误差,相位亦有误差,误差的大小与励磁电流的大小和漏阻抗的大小有关,为减少误差,铁心采用高度硅钢片,且使铁心工作在不饱和状态。根据实际误差的大小,精度分0.5、1.0和3.0三级。

(2)电流互感器

电流互感器的功能是将大电流变为小电流进行测量。其结构特点是原绕组的匝数很少,副绕组的匝数很多。工作时二次侧接电流表或其他测量仪表的电流线圈,相当于工作在短路状态的升压变压器。一次侧电流可为5~2500A ,二次侧电流为5A.

电流互感器亦有变化比和相位误差,按电流比误差的大小,精度分0.2、0.5、1.0、3.0、10.0五级

2.5变电所内的保护设备

2.5.1熔断器

熔断器是一种在通过的电流超过规定值时使其熔体融化而切断电路的保护电路。熔断器的功能主要是对电路及其中设备进行短路保护,但也有的具有过负荷保护的功能。

熔断器有金属熔体、支持熔体的触头装置和外壳组成,当电路中的电流过大时,熔体将被烧断,这样,当电路中过载或短路时,熔断器能迅速切断电路,使电路中的各种电气设备得到保护。断路器的优点是结构简单,价格低,体积小,维护与更换方便,应用广泛。其缺点是不能正常切断或接通电路,而必须与其他电器配合使用;另外,当熔体融化后必须更换,须短时停电。熔断器按电压分为高压熔断器和低压熔断器。

2.5.2变配电所的防雷措施

(1)装设避雷针

室外配电装置应装设避雷针来防护直接雷击。如果变配电所处在附近高建(构)筑物上防雷设施保护范围之内或变配电所本身为室内型时,不必再考虑直击雷的保护。

(2)高压侧装设避雷器

这主要用来保护主变压器,以免雷电冲击波沿高压线路侵入变电所,损坏了变电所的这一最关键的设备。为此要求避雷器应尽量靠近主变压器安装。

避雷器的接地端应与变压器低压侧中性点及金属外壳等连接在一起。在每路进线终端和每段母线上,均装有阀式避雷器。如果进线是具有一段引入电缆的架空线路,则在架空线路终端的电缆头处装设阀式避雷器或排气式避雷器,其接地端与电缆头外壳相联后接地。

避雷器一般与被保护设备并联,正常时避雷器呈绝缘状态,雷电时避雷器被击穿时过电压对大地放电。如下图2.8所示

图2.8 避雷器工作原理图

(3)低压侧装设避雷器

这主要用在多雷区用来防止雷电波沿低压线路侵入而击穿电力变压器的绝缘。当变压器低压侧中性点不接地时(如IT 系统),其中性点可装设阀式避雷器或金属氧化物避雷器或保护间隙。

另外对于架空线路的防雷措施采用架设避雷线。这是防雷的有效措施,但造价高,因此只在66KV 及以上的架空线路上才沿全线装设。35KV 的架空线路上,一般只在变配电所的一段线路上装设。而10KV 及以下的线路上一般不装设避雷线。

2.6补偿设备

采用降低各用电设备所需无功功率可以有效的提高用电企业的自然功率因数,但还不能完全达到要求值,所以需要采用人工补偿装置。

在地铁供电系统中为了提高功率因数采用电力电容器进行功率补偿,使电容的无功与电感的无功相互抵消,通常在低压侧并联补偿电容进行无功补偿;在沈阳地铁供电系统中采用400V 侧补偿电容进行功率补偿,主变电所以及降压式混合所无功率补偿设备。

2.7成套设备

成套设备即使将同一回路的开关电器、测量仪表、保护电路和辅助设备都装配在一个或两个全封闭或半封闭的金属柜中。一般工厂供配电所中常用的成套配电设备有高压成套配电设备和低压成套配电设备。低压成套配电设备只有屋内式一种,高压开关柜则有屋内式和屋外式两种。另外还有一些成套配电设备,如高低压无功功率补偿成套装置,高压综合启动柜,低压动力配电箱及照明配电箱等。

高压成套装置是将断路器、隔离开关、互感器、避雷器、母线等封闭组合在金属壳体内,以绝缘性能和灭弧性能良好的气体作为相间和对地的绝缘措施。高压成套装置是在高电压高容量等级的电网用作受配电及控制。

低压成套装置包括低压配电屏和配电箱,它是将低压一二次设备组装在一起,在低压配电系统中作控制、保护盒计量用。

2.8电力保护系统

电力保护系统是当电力系统出现异常状态时发出信号、减负荷或跳闸的一种自动装置。其保护原理是当短路故障时利用电流、电压、温度等出现变化,构成相应的保护,通过断路器将故障元件能自动地、有选择地、快速地切除。

常用的电力保护有电流保护(例如瞬时电流速断、限时电流速断,过负荷保护等)、电压保护(包括欠压保护、过电压保护)、变压器温度保护、重合闸、整流器内部保护、断路器防跳保护等。

沈阳地铁电力保护系统采用66KV 成套系统保护、35KV 成套系统保护装置和直流开关柜保护。

66KV 成套系统保护配置有电流闭锁电压速断(时间范围0~1S )、定限时过流、限时速断、故障录波、重合闸和断路器防跳功能。

35KV 成套系统保护配置如下:

进线、出线开关柜、馈线柜、母联柜等采用光纤差动、过电流、零序电流、施压保护等;

直流开关柜保护包括瞬时过电流定时限保护、延时过电流定时限保护、热过载反时限保护、电流速度保护、失压保护、双边联跳保护及过电压保护。

3电气主接线

变电所的电气主接线是由变压器、断路器、开关设备、母线等及其连接导线所组成的接受和分配电能的电路。电气主接线反映了变电所的基本结构和功能,在运行中,它能标明电能的输送和分配的关系以及变电所一次设备的运行方式,成为实际运行操作的依据。

3.1电气主接线基本要求

在供电系统设计中,主接线的确定对变电所的设备选择、配电装置布置、继电保护配置忽然计算、自动装置和控制方式选择等都有重大影响。此外,电气主接线对牵引供电系统运行的可靠性、电能质量,运行灵活性和经济性起着决定性作用,因此, 变电所电气主接线方案的缺德必须综合考虑安全性、可靠性、灵活性、经济性等多方面的要求。

此外,对主接线的选择,还应考虑受电容量和受电地点短路容量的大小、用电负荷的重要程度、对电能计量(如高压侧还是低压侧计量、动力及照明分别计费等)及运行操作技术的需要等因素。

3.2主接线的基本接线方式

3.2.1单母线不分段

母线也称汇流排,机会及和分配电能的硬导线。设置母线可以方便的把电源进线和多路引出线通过开关电器连接在一起,以保证供电的可靠性和灵活性。单母线的接线方式如XX 所示,每路进线和出线中都配置有一组开关电器。断路器用于切断和关合正常的负荷电流,并能切断短路电流。隔离开关有两种作用:靠近母线侧的称母线隔离开关,用于隔离母线电源和检修断路器;靠近线路侧的称线路隔离开关,用于防止在检修断路器时从用户侧反向送电,防止雷电过电压沿线路侵入,保证维修人员安全。

图3.1

单母线不分段单母线接线简单,使用设备少,配电装置投资少,但可靠性、灵活性较差。当母线或母线隔离开关故障或检修时,必须断开所有回路,造成全部用户停电。这种接线适用于单电源进线的一般中、小型容量的用户,电压为6~10KV 。 3.2.2单母线分段单母线分段的接线方式如下图所示。这种接线方式引入线有两条回路,母线分成两段,即Ⅰ级和Ⅱ级。每一回路连到一段母线上。两段母线用隔离开关、断路器等开关电器连接形成单母线分段接线。

T1故障,可以将

图3.2 单母线分段

T1切除,由电源

1和电源3.3)

单母线分段便于分段检修母线,减小母线故障影响范围,提高了供电的可靠性和灵活性。这种接线适用于双电源进线的比较重要的负荷,电压为6~10KV 。 3.2.3单母线带旁路接线单母线带旁路接线方式与单母线分段接线方式相比增加了一条母线和一组联络用开关电器,增加了多个线路侧隔离开关。这种接线适合于配电线路较多,负载性质较重要的主变电所或高压配电所。该运行方式灵活,检修设备时可以利用旁路母线供电,减少停电。 3.2.4双母线接线

双母线接线方式采用双电源和两段母线供电,其中两段母线互为备用。该接线适用于负载较重要的用户,运行可靠性和灵活性都较好。它适用的电压为6~10KV 。 3.2.5桥式接线

桥式接线有内桥接线和外桥接线两种,桥式接线能实现电源线路和变压器的充分利用,如变压器2并列给T2供电以减少电源线路中的能耗和电压损失。(接线方式见图

图3.3

QF10跨接在两路电源线之间,犹如一座桥梁,而处在和QF12的内侧,靠近变压器,因此称为内桥式接线。这种主接WL2恢复对变压器T1的供电,这种内桥式结线多用于电源线路

QF11 ,投入QF10 (其两侧

桥式接线可以从接线图中看出两者之间的区别:内桥式,当变压器发生故障时,倒闸操作多,恢复时间长,而当线路发生故障时,倒闸操作少,恢复时间短。而外桥式的操作特点则恰恰与内桥式相反。因此内桥式接线适用于线路较长或不需要经常切换变压器的情况。地铁35kV 总降压变电所是由供电部门提供的,因此线路长是在所难免的,加上内桥式接线是无母线制,这样可以省去母线的投资费用,在形式上,它比单母线分段又少了分段部分的联络部分,这样又可以省去联络柜,综合以上多方面的因素,内桥式接线方式基本综合了前面所述的各种接线方式的优点,满足安全、可靠、灵活、经济的基本要求,因此城市轨道交通常采取内桥式的接线方式。3.3沈阳地铁采用的主接线方案一次侧采用内桥式接线,二次侧采用单母线分段的总降压变电所主电路图。这种主接线,其一次侧的线路断路器QF11线的运行灵活性较好,供电可靠性较高,适用于一、二级负荷工厂。如果某路电源例如WL1线路停电检修或发生故障时,则断开QS 先合),即可由较长因而发生故障和停电检修的机会较多、并且变电所的变压器不需要经常切换的总降压变电所。

4牵引网

4.1牵引网与接触网

牵引网是包括了接触网、钢轨回路(包括大地)、馈电线和回流线的一个大的范畴,它是轨道交通供电系统中向电动车组供电的直接环节。

接触网是一种悬挂在轨道上方沿轨道敷设的和铁路轨顶保持一定距离的输电网。通过电动车组的受电弓(或受电流器)和接触网的滑动接触,牵引电能就由接触网进入电动车组,驱动牵引电动机使列车运行。

馈电线是连接牵引变电所和接触网的导线,它把经牵引变电所变换成合乎牵引制式用的电能馈送给接触网。

轨道在非电牵引情况下只作为列车的导轨。在电力牵引时,轨道除仍具有导轨功能外还需要完成导通回流的任务,因此,电力牵引的轨道,还需要具有畅通导电的性能。

回流线是连接轨道和牵引变电所的导线,通过回流线吧轨道中的回路电流导入牵引变电所。

4.2接触网的工作特点

(1)没有备用

牵引负荷时重要的一级负荷,向牵引变电所供电的电源线均设置两个回路,牵引变电所内主变压器及其他重要设备也在设计中考虑了备用措施,一旦主电源、主要设备故障时,备用电源、备用设备可及时投入运行,以保证对接触网的不间断供电。接触网由于与电动车组在空间上的关系,和轨道一样无法采取备用措施。所以一旦接触网故障,整个供电区间即全部停电,在其间运行的电动车组失去电能供应,列车停运。 (2)经常处在动态运行状态中

和一般的电力线路只在两点间固定传输电能的作用不同,在接触网下沿线有许多电动车组告诉运动取流。电动车组受电弓(或受流器)以对接触网一定的压力和速度与接触网接触摩擦运行,通过接触网的电流很大。运行中不可避免地会产生受电弓离线而引起电弧,再加上在露天区段还要承受风、雾、雨、雪及大气污染的作用,使接触网昼夜不停的处在振动、摩擦、电弧、污染、伸缩的动态运行之中。这些因素对接触网各种线索、零件都产生恶劣影响,使其发生故障的可能性较一般电力线路的概率要大得多。 (3)结构复杂,技术要求高

接触网的运行环境和运行特点决定了接触网的结构较一般电力线路有很大的不同,为了保证电动车组安全、可靠、质量良好地从接触网取流,接触网的结构比较复杂,技术要求也比较高,如对接触网导线的高度、拉力值、定位器的坡度,接触网的弹性、均匀度等都有定量的要求。

4.3对接触网的基本要求

接触网的故障状态主要是指接触网与电动车组受电弓(或受流器)滑板的接触和导电情况。从电路要求上,为保证良好的导电情况,滑板与接触线的接触应保持一定的接触压力。在电动车组静止时,接触压力可以保持不变。当电动车组运行时,滑板跟着运动,与接触网形成滑动摩擦接触。这时,如能继续保持一定的接触压力,不间断的向电动车组供电,接触网才处于良好的跟着状态。因此,为了尽量保证对电动车组良好的供电,对接触网有一些基本的要求: (1). 接触网悬挂硬弹性均匀、高度一致,在高速行车和恶劣的气象条件下,能保证正常取流。

(2). 接触网结构应力求简单,并保证在施工和运营检修方面具有充分的可靠性和灵活性。

(3). 接触网的寿命应尽量长,具有足够的耐磨性和抗腐蚀能力。

(4). 接触网的建设应注意节约有色金属及其他车贵重材料,以降低成本。 4.4接触网的分类及其特点

接触网分为架空式接触网和接触轨式接触网(又称第三轨)。架空式接触网用于城市地面或地下、铁路干线、工矿的电力牵引线路。接触轨式接触网一般用于净空受限的地下电力牵引。我国在地铁轨道系统中,架空式和接触轨式均有采用。我国北京地铁采用的是接触轨式接触网,上海和广州均采用了架空式接触网。

4.4.1接触轨式馈电方式的特点

城市轨道交通的接触轨馈电方式中向车辆馈电的接触轨(根据集电靴和接触轨配合的方式,分为上磨式、上磨式和侧磨式等形式,如图4.1所示) 设置在车辆的走行轨旁。上磨式接触轨结构如图4.2所示,主要由接触轨、端部弯头、防爬器、隔离开关和防护罩等组成,并由绝缘子支撑。与之相配合,车辆采用集电靴受流。接触轨具有使用寿命长、维修量小、结构简单和运行费用低等优点,它能充分利用隧道空间,但接触轨系统距地面很近无法做到全方位的人员接近防护,在隧道内保养、检修或在车库内检修时应特别注意安全。

图4.1接触轨结构分类

图4.2 上磨式接触轨结构

另外某些城市车辆采用与上磨式接触轨配合的上磨式集电靴。在国内,北京地铁和城轨、天津地铁,在建的武汉城轨采用这种方式。上磨式集电靴这种方式一般适用于DC750V 电压供电,国外有个别城市有采DCl000V 电压供电而仍然使用接触轨馈电,并且车辆最高运行速度一般在90 km/h 以下。 4.4.2接触网馈电方式的特点

城市轨道交通的接触网馈电方式中向车辆馈电的接触网设置在车辆的走行轨上方,沿走行轨中心呈“之”字形走向,有柔性悬挂、弹性悬挂和刚性悬挂三种

方式,弹性悬挂和刚性悬挂方式只能用于隧道中。柔性悬挂方式的接触网采用全

补偿(正线) 或半补偿(站场或岔线) 简单链型悬挂,由接触导线、承力索、吊弦、导电连接线、辅助馈电线、绝缘子、坠坨和支持装置等构成;弹性悬挂则需要采用特制的专用弹性定位器,由接触导线、导电连接线、辅助馈电线、弹性定位器等构成;刚性悬挂方式的接触网则由接触导线、汇流排和绝缘子等构成。与之相配合,车辆采用受电弓受流。 (1)柔性悬挂。

这种悬挂形式不受线路位置的影响。在隧道内采用这种悬挂方式约需要500 mm 左右的安装空间,接触网张力约30 kN,全补偿。在国内,广州l 号线全线、上海地铁l 号线地面段、明珠线和在建的广州2号线地面段、深圳地铁全线和天津城轨滨海线采用了这种方式。地面上的接触网采用柔性悬挂形式。考虑到地面存在大气雷电的侵害, 因此随接触网架设有一条接地保护线, 并且在站场等重要场所增设避雷器。为了保证受电弓运行的连续性,通常在采用弹性悬挂和刚性悬挂接触网的隧道口设置一定距离的过渡段,然后再与柔性接触网连接。 (2)弹性悬挂

这种悬挂方式仅适用于隧道,需要采用一种悬挂专用的弹性定位器,接触网张力约1 5kN,半补偿。在国内,上海地铁1号线就在隧道中采用了弹性悬挂方式。采用这种方式需要约450 mm左右的安装空间。实验室内的单导线隧道简单弹性悬挂,对于城市轨道交通,这种悬挂方式通常采用双导线简单弹性悬挂。 (3)刚性悬挂。

这种悬挂方式同样仅适用于隧道。刚性悬挂实际上就是把第三轨放置在了隧道的顶部,安装高度约400 mm,但需要借助特殊的安装工具。在国内,广州地铁2号线中的地下线路将采用这种方式。

接触轨和接触网馈电方式的经济、技术综合性能比较见表4.3:

表4.3接触轨和接触网馈电方式的比较

5电力监控

在城市轨道交通系统中控制中心肩负着指挥中心和地铁运营的信息收发中心的使命。控制中心监控系统起着保证地铁全线安全运营和监视控制沿线信息的作用,其中设有电力监控,负责统一指挥全线供电设备运行。

5.1电力监控系统概述

电力监控SCADA (Supervisory Control And Data Acquisition)又称为远动监控和数据采集,主要用以实现对远方电力运行设备的监视和控制,以提高供电安全运行水平。

电力监控系统主要通过“四遥”实现其监控功能,即遥控、遥测、遥信和遥调。遥控是调度所对远方变电站被控对象(开关等)进行操作;遥测是将变电站被测对象的数值(电流、电压等)传送到调度所;遥信是将变电站被控对象(开关位置等)的状态信息传送到调度所;遥调是调度所对远方变电站工作状态和参数(变压器输出电压等)进行调整。另外电力监控系统还具有其他管理功能,例如报表管理、事故回放、故障分析、信息管理和技能培训等功能。

城市轨道交通电力监控系统采用分层分布式结构,即有调度控制中心、车辆段监控和供电复示系统、主变电所系统及车站变电所子站系统。

5.2沈阳地铁电力监控系统

沈阳地铁电力监控系统组成示意图5.2如下

图5.2沈阳地铁电力监控系统组成示意图

沈阳地铁一号线中央监控系统中控制中心选用DSC-9000U 自动化系统,其主要设备包括以太网交换机、系统服务器、web 服务器、打印服务器、操作员工作站、系统维护工作站、网络打印机以及网络连接附件等

变电所自动化综合系统采用国电南自NDT650自动化系统,其采用分层分布式结构,即站级管理层、网络通信层和间隔设备层。

站间管理层设备包括控制信号盘及盘内的通信交换机、交换机、一体化监控计算机;

网络通信层是两个独立的以太网接口,互为备用;

间隔管理层是分散安装于供电设备就地的微机保护测控、信息采集等装置。

结束语

供电系统是地铁所有用电用户的电能源泉,是机车和机电系统运行的动力保证。一旦供电系统发生故障,将使整条线路失去运营能力,造成重大经济损失。随着地铁线路的不断增多,地铁供电系统复杂程度越来越高,出现事故的可能性和故障波及的范围、造成的损失也不断增大。供电系统能否安全可靠运行将直接关系到地铁的安全、稳定运营,为了保证地铁安全可靠地运行,探讨其供电系统安全措施是极其有意义的。

本文通过分析城市轨道交通供电系统的各个组成部分,加深对地铁供电系统的了解,同时也加强了我本人搜集,整理、分析资料的能力,对我以后的工作、学习将产生极大的帮助。

【参考文献】

【1】 郑瞳炽,张明锐. 《城市轨道交通牵引供电系统》,中国铁道出版社,2009,22-88

【2】 张莹. 《工厂供配电技术》,电子工业出版社,2009,59-67

【3】 韩利民. 《地铁运营安全及对策研究》中国安全科学学报,2004,45~60

【4】 沈阳地铁岗前培训资料

【5】 徐安,陶生桂. 《城市轨道交通电力牵引》,中国铁道出版社,2000.3,90~112

【6】 孙有望,李云清. 《城市轨道交通概论》,中国铁道出版社,2008.8,3~25

毕业设计文件

设计题目: 城市轨道交通供电系统概述与分析———— 专业:

指导教师:

摘要:

近几年来,随着我国大城市交通压力的逐渐增大,城市轨道交通系统的发展步伐亦逐日加快。本文主要介绍了城市轨道交通供电系统的构成以及详细介绍了各部分的功能及分类,总结了国内外各城市地铁供电系统的应用方式。

因本人专业偏向于弱电,所以本文在全面总结城市轨道供电系统的前提下,着重介绍了变电所内的二次设备,从设备的种类、分类、用途以及构造方面加以了解。同时以沈阳地铁为案例介绍、分析了此轨道交通供电系统方案。

关键词:轨道交通 供电系统 二次设备 Abstract :

In recent years, with the city traffic pressure increase gradually, the development of urban rail transit system is accelerated pace of daily. This paper mainly introduces the power supply system of urban rail transit are introduced in detail the composition and function of each part and classification, summarizes the domestic and international every city metro power system application.

Because I am in favour of professional, so this weak in comprehensive summary of urban rail power supply system, emphatically introduces the condition of equipment, within the substation equipment types, from classification, applications and structural aspects. In case of shenyang subway is introduced and analyzed the rail traffic system.

Key words: Rail transit Power supply system Second equipment

目录

1城市轨道交通供电系统构成 ................................. 8 1.1地铁供电系统的组成 ..................................... 8 1.2牵引电力制式 .......................................... 10 2变电所的主要电气设备 .................................... 12 2.1变电所的分类 .......................................... 12 2.2变压器的工作原理、分类及结构 .......................... 13 2.2.1变压器的工作原理 .................................... 13 2.2.2变压器的分类及结构 .................................. 13 2.2.3变压器型号与额定值意义 .............................. 14 2.4变电所内的开关设备 .................................... 15 2.4.1高压断路器 .......................................... 15 2.4.2隔离开关 ............................................ 15 2.4.3负荷开关 ............................................ 16 2.4.4互感器 .............................................. 16 2.5变电所内的保护设备 .................................... 17

2.5.1熔断器 .............................................. 17 2.5.2变配电所的防雷措施 .................................. 17 2.6补偿设备 .............................................. 18 2.7成套设备 .............................................. 18 2.8电力保护系统 .......................................... 18 3电气主接线 .............................................. 20 3.1电气主接线基本要求 .................................... 20 3.2主接线的基本接线方式 .................................. 20 3.2.1单母线不分段 ........................................ 20 3.2.2单母线分段 .......................................... 21 3.2.3单母线带旁路接线 .................................... 22 3.2.4双母线接线 .......................................... 22 3.2.5桥式接线 ............................................ 22 3.3沈阳地铁采用的主接线方案 .............................. 23 4牵引网 .................................................. 24 4.1牵引网与接触网 ........................................ 24

4.2接触网的工作特点 ...................................... 24 4.3对接触网的基本要求 .................................... 25 4.4接触网的分类及其特点 .................................. 25 4.4.1接触轨式馈电方式的特点 .............................. 25 4.4.2接触网馈电方式的特点 ................................ 26 5电力监控 ................................................ 29 5.1电力监控系统概述 ...................................... 29 5.2沈阳地铁电力监控系统 .................................. 29 结束语 . ................................................... 31 【参考文献】 . ............................................. 32

城市轨道交通供电系统概述及分析

前言

世界上地铁交通很早就作为公共交通在城市中出现。随着科学技术和城市化的发展,大运量的地铁交通在现代大城市中越来越起着重要的作用。经济发达国家城市的交通发展历史告诉我们,只有采用大客运量的地铁交通系统,才是从根本上改善城市公共交通状况的有效途径。

我国发展地铁交通的历史也并不短,40年前北京就开始了地铁建设。想建地铁的城市也不少, 但一直因造价太贵而却步。至今一些百万人口以上的大城市, 仍然用传统的公共汽车和无轨电车来维持客运的做法, 已越来越不能满足城市居民高频率出行的需要。因而目前很多大城市又在考虑和策划修建地铁交通项目,除北京外, 上海﹑广州等城市也有地铁线路在运营, 但远不能较为普遍地满足需要。由于我国城市地铁交通的应用技术和基础理论都还处于开拓阶段, 项目实施的大多数情况是要引进技术和设备, 国产化率低, 成为工程造价昂贵的主要原因。因而提高我国城市地铁交通行业的技术力量, 发挥自主建设能力, 努力降低工程价, 已是健康发展大运量地铁交通的关键。

电力牵引供电系统是城市轨道交通的重要组成部分, 没有电力牵引供电系统的可靠安全供电, 就不可能有城市轨道交通的正常运行。为此, 本文对电力牵引供电系统的特点作了深入的分析和研究。

1城市轨道交通供电系统构成

通常国家供电系统总是把在同一区域(或大区)的许多发电厂通过高压输电线和变电所连接起来成为一个大的统一的供电系统,向该区域的负荷供电,这样由各级电压输电线将发电厂、变电所和电力用户联接起来的一个发电、输电、变电、配电和用户的统一体称为电力系统。

地铁用电取自城市电网,经过地铁供电系统实现输送和变换,应适当的电压等级共给地铁各类设备,例如电力机车、照明、通风、空调、排水、自动扶梯、自动检票机等用电设备。

1.1地铁供电系统的组成

城市轨道交通系统的组成包括牵引供电系统和动力照明供电系统,如图1.1所示:

图1.1 城市轨道交通规定系统组成

城市轨道交通系统是一级电力负荷,安全、可靠是供电系统的主要目的。在地铁供电系统中,牵引供电系统由于直接给列车提供动力,占据着举足轻重的地位。该系统的好坏直接影响整个地铁供电系统质量的高低。如果该系统出现问题,小则影响某个变电站、几个供电区间的输送电,大则引起整个牵引供电系统

的崩溃,给地铁列车的正常运营造成影响,因此要保证安全可靠的供电需要采用两路独立电源供电和增设应急电源。

在城市轨道交通供电系统中,从发电厂经升压、高压输电网、区域变电站至主降压变电站部分通常被称为牵引供电系统的“外部(或一次)供电系统”。

从主降压变电所(当它不属于电力部门时)及其以后部分统称为“牵引供电系统”。它应该包括:主变电所、直流牵引变电所、馈电线、接触网、走行轨及回流线等。直流牵引变电所将三相高压交流电变成适合电动车辆应用的低压直流电。馈电线是将牵引变电所的直流电送到接触网上。接触网是沿列车走行轨架设的特殊供电线路,电动车辆通过其受流器与接触网的直接接触而获得电力。走形轨道构成牵引供电回路的一部分。回流线将轨道回流引向牵引变电所。

牵引供电系统组成包括以下几个方面,如图1.2所示:

图1.2牵引供电系统组成

城市轨道交通供电系统负荷可分为一级重要负荷和二级、三级负荷,其中一级重要负荷包括防灾报警、事故照明、通信信号、通风消防,对于一级重要负荷若中断供电将可能发生中毒、爆炸和火灾危险,因此须保证两路独立电源供电,并备有应急电源,而其他用电设备,例如电梯、一般照明、普通风机、排污泵等则属于二级、三级负荷。

在正常情况下,变电所同时向各个负荷供电,如若供电系统发生故障或者出现事故时,则断开二、三级负荷,优先向一级负荷供电,以最大限度地保证地铁安全。

如图1.3所示:

图1.3 400V低压系统简图

1.2牵引电力制式

在城市轨道交通中电力机车必须能产生足够大的牵引力,具有较高的过载能力,并能充分利用牵引电机容量,容易实现调速以及先进的经济技术指标的特点,常采用直流电机和交流电机两大类,同时各有优缺点。

对于直流电机来说,启动和调速容易实现,但电机结构复杂、成本高,且接通电源瞬间启动电流太大,串联大功率电阻限流和降压使能量损耗大,北京一号线采用直流电机。

而交流电机性价比高于直流电机,寿命长,几乎免于维护,特别是调压调频逆变器系统使启动和调速更容易实现,较为普遍使用。

在城市轨道交通的牵引制式中 ,直流制比同电压交流制供电的电压损失

小,且地铁适于电压较低的供电电压,因此城市交通通常采用低电压的直流供电制式,国际拟定标准有600 V、750V ,我国国标为750V 、1500V ;北京、天津采用DC750 V牵引制式,电压波动范围为DC500V ~DC900V ,上海、广州、沈阳等采用DC1500V 牵引制式,电压波动范围为DC1000V ~DC1800V 。

沈阳地铁牵引系统受电方式是牵引系统通过受电弓从DC1500V 接触网受电,每列车配备两台DC110V 电动气泵,升弓时间不大于8秒,降弓时间不大于7秒,沈阳地铁采用日本三菱交流异步电动机牵引,且采用1C4M 供电方式,即由一台牵引逆变器向四台并联电机提供变频变压三相电源,从而驱动机车。

2变电所的主要电气设备

变电所是用以实现切断或接通、改变或者调整电压的功能。

变电所内的电气设备按所属电路性质分为两大类:一次高压电路中所有的电气设备,即为一次设备;二次控制、信号和测量电路中的所有电气设备即为二次设备。

一次设备按其在一次电路中的功用又可分为变换设备、控制设备、保护设

备、补偿设备和成套设备等类型。

(1) 变换设备

用以变换电能电压或电流的设备。如电力变压器、整流器、电压互感器、电

(2)控制设备

用以控制电路通断的设备。如各种高低压开关设备。

(3)保护设备

用以保护电路过电流或过电压的设备。如高低压熔断器和避雷器等。

(4)补偿设备

用以补偿电路的无功功率以提高系统功率因数的设备。如高低压电容器、静止无功补偿设备等。

(5)成套设备

按一定的线路方案将有关一次、二次设备组合而成的设备。 如高压开关

柜,低压配电屏,高低压电容柜和成套变电站等。 流互感器等 。

2.1变电所的分类

变电所是供配电系统的核心,在供电系统中占有特别重要的地位。在城市轨道交通供电系统中,变电所可分为主变电所,牵引变电所,降压变电所

交流牵引变电所又分为工频交流牵引变电所和低频交流牵引变电所,工频交流牵引变电所是将电网电压经变压器降为25~50KV 交流电压供给电力机车,而低频交流牵引变电所经降压变频换为162/3Hz低频交流电压。对于直流牵引变电所是将电网电压经降压整流为相应等级的直流电供给城市轨道交通系统中的电力机车,其中整流是区别于交流牵引变电所最关键设备。降压整流为直流电的直流牵引变电所和车站区间供电的降压变电所合并为牵引降压变电所。

沈阳地铁一号线一期及延长线设置两座66KV/35 KV主变电所:重工街、三经街;每座主变电所由地区变电所引入两回路互相独立的6 6KV电源,变换为35 KV 输出。

设置十座牵引降压变电所:车辆段混合所、十三号街、黎明文化宫等;牵引降压变电所将输入的AC35 KV电压变换为AC1500V 和DC400 V,分别供给牵引网和动力照明配电系统。

设置降压变电所十三座:中央大街、沈阳站、青年大街等,降压变电所将输入的AC35 KV电压变换为DC400 v,供给动力照明配电系统。

另外在车辆段和控制中心设置两座跟随市降压变电所,将输入的AC35 KV电压变换为DC400 v,供给动力照明配电系统及控制系统。

2.2变压器的工作原理、分类及结构

变压器是一种静止的电器,它通过线圈间的电磁感应作用,把一种电压的电能转换为同频率的另一种电压的电能,故称变压器。实际上,它在变压的同时还能改变电流,还可改变阻抗和相数。

2.2.1变压器的工作原理

变压器的主要部件是一个铁心和套在铁心上的两个绕组,如图2.1所示。

图2.1 变压器构成简图

理想状况如下(不计电阻、铁耗和漏磁),原绕组加电压 U1 ,产生电流 I1 ,建立磁通ø ,沿铁心闭合,分别在原副绕组中感应电动势e1 和 e2 。

2.2.2变压器的分类及结构

按用途分:电力变压器和特种变压器。

按绕组数目分:单绕组(自耦)变压器、双绕组变压器、三绕组变压器和多绕组变压器。

按相数分:单相变压器、三相变压器和多相变压器。

按铁心结构分:心式变压器和壳式变压器。

按冷却介质和冷却方式分:干式变压器、油浸式变压器和充气式变压器 图2.2为油浸式变压器:

图2.2 油浸式变压器

(1)铁心

作用:变压器的主磁路;

材料:为了提高导磁性能和减少铁损,用0.35mm 厚、表面涂有绝缘漆的硅钢片叠成;基本形式:心式和壳式。

(2)绕组

变压器的一次绕组和二次绕组一般用绝缘铜线或铝线绕制而成圆筒形的多层线圈,放在铁芯柱上,导体外面采用绝缘处理。 基本形式:同心式和交叠式 。

(3)油箱及其附件

油箱、储油柜、散热器、分接开关、套管、气体继电器等。

油箱:油浸式变压器的器身浸在变压器油的油箱中。油是冷却介质,又是绝缘介质。油箱侧壁有冷却用的管子(散热器或冷却器)。

绝缘套管将线圈的高、低压引线引到箱外,是引线对地的绝缘,担负着固定的作用。

2.2.3变压器型号与额定值意义

型号表示一台变压器的结构、额定容量、电压等级、冷却方式等内容,表示方法为如图2.3:

图2.3变压器型号与额定值意义

在现代电力系统中,常采用多台变压器并联运行的方式。并联运行是将几台变压器的原、副绕组分别接到公共的母线上共同对负载供电的运行方式。变压器并联运行的条件为一次二次额定电压必须对应相等,且连接组别和短路电压须相同,以及容量尽量相同或相近。

在沈阳地铁供电系统中,各主变电所配有两台主变变压器(并联运行),三相油浸自冷双线圈有载调压降压电力变压器,型号为SZ11-31500KVA/66KV,即一次电压66KV ,容量31500KVA ;动力变压器采用AC35/0.4KV、额定功率为

1000KVA 、2000KVA 、1600KVA 的户内干式风冷式变压器;在各牵引降压混合所设置两台牵引整流变压器,采用ZQSC9-2200/35的包封式环氧树脂浇注绝缘结构干式变压器。

2.4变电所内的开关设备

2.4.1高压断路器

断路器又叫高压开关,它是变电所的重要设备之一。断路器不仅可以切断与闭合高压电路的空载电流和负载电流,而且,当系统发生故障时,它与保护装置、自动装置相配合,可以迅速地切断故障电流,以减少停电范围,防止事故扩大,保证系统的安全运行。

断路器的主要结构大体分为倒流部分、灭弧部分、绝缘部分和操作机构部分。断路器在闭合时起接通回路的作用,当断路器断开时,触头虽已分开,但触头间仍会产生电弧,因而断路器应具有灭弧能力。断路器的灭弧方式有多种,从灭弧方式上可以将断路器分为:油断路器、六氟化流断路器、真空断路器等。

2.4.2隔离开关

隔离开关是没有灭弧装置的开关电器,在分闸状态下有明显的断口,在合闸状态下能可靠的通过额定电流和短路电流。因隔离开关没有灭弧装置,不能切断负荷电流和短路电流,因此隔离开关通常和断路器配合使用,且在操作中必须注意与断路器操作的先后顺序。当合闸时,先合隔离开关,后合断路器;分闸时,先分断路器,后分隔离开关。这种操作通常称为倒闸操作。为了保证安全,一般采用连锁装置,以防止误操作。

隔离开关的主要用途有:

(1)为设备或线路的检修和分段进行电气隔离;

(2)在断口两段电位接近相等的情况下,倒换母线,改变接线方式;

(3)分合一定长度的母线和电缆;

(4)分合一定容量的空载变压器,一定长度的空载线路和电压互感器。

2.4.3负荷开关

负荷开关是在高压隔离开关的基础上加入简单的灭弧装置而成的,能切、合负荷电流,但不能切断短路电流。因此,负荷开关必须与高压断路器配合使用,短路电流由熔断器切断,而它专门在高压装置中通断负荷电流,也能在过负荷的情况下自动跳闸。

负荷开关常在一些经常需要进行分、合闸的地方使用。负荷开关的结构与断路器相似,制式开断性能要求比断路器低。因此,构造比断路器简单,操作机构动力较小,价格也较断路器低。

除了以上开关设备外,变电所内常用的还有低压刀开关、低压刀熔开关、低压断路器、直流开关等开关设备。

2.4.4互感器

互感器是一种特殊变压器,有电压互感器和电流互感器,其主要功能有变换、隔离保护功能,以及扩大仪表、继电器等二次设备应用范围。

(1)电压互感器

电压互感器的功能是将高电压变为低电压进行测量、控制。其结构特点是原绕组匝数很多,副绕组匝数很少,相当于特殊的降压变压器。工作时二次侧接电压表、继电器等,一般为100V ,相当于开路。

互感器的电压比有误差,相位亦有误差,误差的大小与励磁电流的大小和漏阻抗的大小有关,为减少误差,铁心采用高度硅钢片,且使铁心工作在不饱和状态。根据实际误差的大小,精度分0.5、1.0和3.0三级。

(2)电流互感器

电流互感器的功能是将大电流变为小电流进行测量。其结构特点是原绕组的匝数很少,副绕组的匝数很多。工作时二次侧接电流表或其他测量仪表的电流线圈,相当于工作在短路状态的升压变压器。一次侧电流可为5~2500A ,二次侧电流为5A.

电流互感器亦有变化比和相位误差,按电流比误差的大小,精度分0.2、0.5、1.0、3.0、10.0五级

2.5变电所内的保护设备

2.5.1熔断器

熔断器是一种在通过的电流超过规定值时使其熔体融化而切断电路的保护电路。熔断器的功能主要是对电路及其中设备进行短路保护,但也有的具有过负荷保护的功能。

熔断器有金属熔体、支持熔体的触头装置和外壳组成,当电路中的电流过大时,熔体将被烧断,这样,当电路中过载或短路时,熔断器能迅速切断电路,使电路中的各种电气设备得到保护。断路器的优点是结构简单,价格低,体积小,维护与更换方便,应用广泛。其缺点是不能正常切断或接通电路,而必须与其他电器配合使用;另外,当熔体融化后必须更换,须短时停电。熔断器按电压分为高压熔断器和低压熔断器。

2.5.2变配电所的防雷措施

(1)装设避雷针

室外配电装置应装设避雷针来防护直接雷击。如果变配电所处在附近高建(构)筑物上防雷设施保护范围之内或变配电所本身为室内型时,不必再考虑直击雷的保护。

(2)高压侧装设避雷器

这主要用来保护主变压器,以免雷电冲击波沿高压线路侵入变电所,损坏了变电所的这一最关键的设备。为此要求避雷器应尽量靠近主变压器安装。

避雷器的接地端应与变压器低压侧中性点及金属外壳等连接在一起。在每路进线终端和每段母线上,均装有阀式避雷器。如果进线是具有一段引入电缆的架空线路,则在架空线路终端的电缆头处装设阀式避雷器或排气式避雷器,其接地端与电缆头外壳相联后接地。

避雷器一般与被保护设备并联,正常时避雷器呈绝缘状态,雷电时避雷器被击穿时过电压对大地放电。如下图2.8所示

图2.8 避雷器工作原理图

(3)低压侧装设避雷器

这主要用在多雷区用来防止雷电波沿低压线路侵入而击穿电力变压器的绝缘。当变压器低压侧中性点不接地时(如IT 系统),其中性点可装设阀式避雷器或金属氧化物避雷器或保护间隙。

另外对于架空线路的防雷措施采用架设避雷线。这是防雷的有效措施,但造价高,因此只在66KV 及以上的架空线路上才沿全线装设。35KV 的架空线路上,一般只在变配电所的一段线路上装设。而10KV 及以下的线路上一般不装设避雷线。

2.6补偿设备

采用降低各用电设备所需无功功率可以有效的提高用电企业的自然功率因数,但还不能完全达到要求值,所以需要采用人工补偿装置。

在地铁供电系统中为了提高功率因数采用电力电容器进行功率补偿,使电容的无功与电感的无功相互抵消,通常在低压侧并联补偿电容进行无功补偿;在沈阳地铁供电系统中采用400V 侧补偿电容进行功率补偿,主变电所以及降压式混合所无功率补偿设备。

2.7成套设备

成套设备即使将同一回路的开关电器、测量仪表、保护电路和辅助设备都装配在一个或两个全封闭或半封闭的金属柜中。一般工厂供配电所中常用的成套配电设备有高压成套配电设备和低压成套配电设备。低压成套配电设备只有屋内式一种,高压开关柜则有屋内式和屋外式两种。另外还有一些成套配电设备,如高低压无功功率补偿成套装置,高压综合启动柜,低压动力配电箱及照明配电箱等。

高压成套装置是将断路器、隔离开关、互感器、避雷器、母线等封闭组合在金属壳体内,以绝缘性能和灭弧性能良好的气体作为相间和对地的绝缘措施。高压成套装置是在高电压高容量等级的电网用作受配电及控制。

低压成套装置包括低压配电屏和配电箱,它是将低压一二次设备组装在一起,在低压配电系统中作控制、保护盒计量用。

2.8电力保护系统

电力保护系统是当电力系统出现异常状态时发出信号、减负荷或跳闸的一种自动装置。其保护原理是当短路故障时利用电流、电压、温度等出现变化,构成相应的保护,通过断路器将故障元件能自动地、有选择地、快速地切除。

常用的电力保护有电流保护(例如瞬时电流速断、限时电流速断,过负荷保护等)、电压保护(包括欠压保护、过电压保护)、变压器温度保护、重合闸、整流器内部保护、断路器防跳保护等。

沈阳地铁电力保护系统采用66KV 成套系统保护、35KV 成套系统保护装置和直流开关柜保护。

66KV 成套系统保护配置有电流闭锁电压速断(时间范围0~1S )、定限时过流、限时速断、故障录波、重合闸和断路器防跳功能。

35KV 成套系统保护配置如下:

进线、出线开关柜、馈线柜、母联柜等采用光纤差动、过电流、零序电流、施压保护等;

直流开关柜保护包括瞬时过电流定时限保护、延时过电流定时限保护、热过载反时限保护、电流速度保护、失压保护、双边联跳保护及过电压保护。

3电气主接线

变电所的电气主接线是由变压器、断路器、开关设备、母线等及其连接导线所组成的接受和分配电能的电路。电气主接线反映了变电所的基本结构和功能,在运行中,它能标明电能的输送和分配的关系以及变电所一次设备的运行方式,成为实际运行操作的依据。

3.1电气主接线基本要求

在供电系统设计中,主接线的确定对变电所的设备选择、配电装置布置、继电保护配置忽然计算、自动装置和控制方式选择等都有重大影响。此外,电气主接线对牵引供电系统运行的可靠性、电能质量,运行灵活性和经济性起着决定性作用,因此, 变电所电气主接线方案的缺德必须综合考虑安全性、可靠性、灵活性、经济性等多方面的要求。

此外,对主接线的选择,还应考虑受电容量和受电地点短路容量的大小、用电负荷的重要程度、对电能计量(如高压侧还是低压侧计量、动力及照明分别计费等)及运行操作技术的需要等因素。

3.2主接线的基本接线方式

3.2.1单母线不分段

母线也称汇流排,机会及和分配电能的硬导线。设置母线可以方便的把电源进线和多路引出线通过开关电器连接在一起,以保证供电的可靠性和灵活性。单母线的接线方式如XX 所示,每路进线和出线中都配置有一组开关电器。断路器用于切断和关合正常的负荷电流,并能切断短路电流。隔离开关有两种作用:靠近母线侧的称母线隔离开关,用于隔离母线电源和检修断路器;靠近线路侧的称线路隔离开关,用于防止在检修断路器时从用户侧反向送电,防止雷电过电压沿线路侵入,保证维修人员安全。

图3.1

单母线不分段单母线接线简单,使用设备少,配电装置投资少,但可靠性、灵活性较差。当母线或母线隔离开关故障或检修时,必须断开所有回路,造成全部用户停电。这种接线适用于单电源进线的一般中、小型容量的用户,电压为6~10KV 。 3.2.2单母线分段单母线分段的接线方式如下图所示。这种接线方式引入线有两条回路,母线分成两段,即Ⅰ级和Ⅱ级。每一回路连到一段母线上。两段母线用隔离开关、断路器等开关电器连接形成单母线分段接线。

T1故障,可以将

图3.2 单母线分段

T1切除,由电源

1和电源3.3)

单母线分段便于分段检修母线,减小母线故障影响范围,提高了供电的可靠性和灵活性。这种接线适用于双电源进线的比较重要的负荷,电压为6~10KV 。 3.2.3单母线带旁路接线单母线带旁路接线方式与单母线分段接线方式相比增加了一条母线和一组联络用开关电器,增加了多个线路侧隔离开关。这种接线适合于配电线路较多,负载性质较重要的主变电所或高压配电所。该运行方式灵活,检修设备时可以利用旁路母线供电,减少停电。 3.2.4双母线接线

双母线接线方式采用双电源和两段母线供电,其中两段母线互为备用。该接线适用于负载较重要的用户,运行可靠性和灵活性都较好。它适用的电压为6~10KV 。 3.2.5桥式接线

桥式接线有内桥接线和外桥接线两种,桥式接线能实现电源线路和变压器的充分利用,如变压器2并列给T2供电以减少电源线路中的能耗和电压损失。(接线方式见图

图3.3

QF10跨接在两路电源线之间,犹如一座桥梁,而处在和QF12的内侧,靠近变压器,因此称为内桥式接线。这种主接WL2恢复对变压器T1的供电,这种内桥式结线多用于电源线路

QF11 ,投入QF10 (其两侧

桥式接线可以从接线图中看出两者之间的区别:内桥式,当变压器发生故障时,倒闸操作多,恢复时间长,而当线路发生故障时,倒闸操作少,恢复时间短。而外桥式的操作特点则恰恰与内桥式相反。因此内桥式接线适用于线路较长或不需要经常切换变压器的情况。地铁35kV 总降压变电所是由供电部门提供的,因此线路长是在所难免的,加上内桥式接线是无母线制,这样可以省去母线的投资费用,在形式上,它比单母线分段又少了分段部分的联络部分,这样又可以省去联络柜,综合以上多方面的因素,内桥式接线方式基本综合了前面所述的各种接线方式的优点,满足安全、可靠、灵活、经济的基本要求,因此城市轨道交通常采取内桥式的接线方式。3.3沈阳地铁采用的主接线方案一次侧采用内桥式接线,二次侧采用单母线分段的总降压变电所主电路图。这种主接线,其一次侧的线路断路器QF11线的运行灵活性较好,供电可靠性较高,适用于一、二级负荷工厂。如果某路电源例如WL1线路停电检修或发生故障时,则断开QS 先合),即可由较长因而发生故障和停电检修的机会较多、并且变电所的变压器不需要经常切换的总降压变电所。

4牵引网

4.1牵引网与接触网

牵引网是包括了接触网、钢轨回路(包括大地)、馈电线和回流线的一个大的范畴,它是轨道交通供电系统中向电动车组供电的直接环节。

接触网是一种悬挂在轨道上方沿轨道敷设的和铁路轨顶保持一定距离的输电网。通过电动车组的受电弓(或受电流器)和接触网的滑动接触,牵引电能就由接触网进入电动车组,驱动牵引电动机使列车运行。

馈电线是连接牵引变电所和接触网的导线,它把经牵引变电所变换成合乎牵引制式用的电能馈送给接触网。

轨道在非电牵引情况下只作为列车的导轨。在电力牵引时,轨道除仍具有导轨功能外还需要完成导通回流的任务,因此,电力牵引的轨道,还需要具有畅通导电的性能。

回流线是连接轨道和牵引变电所的导线,通过回流线吧轨道中的回路电流导入牵引变电所。

4.2接触网的工作特点

(1)没有备用

牵引负荷时重要的一级负荷,向牵引变电所供电的电源线均设置两个回路,牵引变电所内主变压器及其他重要设备也在设计中考虑了备用措施,一旦主电源、主要设备故障时,备用电源、备用设备可及时投入运行,以保证对接触网的不间断供电。接触网由于与电动车组在空间上的关系,和轨道一样无法采取备用措施。所以一旦接触网故障,整个供电区间即全部停电,在其间运行的电动车组失去电能供应,列车停运。 (2)经常处在动态运行状态中

和一般的电力线路只在两点间固定传输电能的作用不同,在接触网下沿线有许多电动车组告诉运动取流。电动车组受电弓(或受流器)以对接触网一定的压力和速度与接触网接触摩擦运行,通过接触网的电流很大。运行中不可避免地会产生受电弓离线而引起电弧,再加上在露天区段还要承受风、雾、雨、雪及大气污染的作用,使接触网昼夜不停的处在振动、摩擦、电弧、污染、伸缩的动态运行之中。这些因素对接触网各种线索、零件都产生恶劣影响,使其发生故障的可能性较一般电力线路的概率要大得多。 (3)结构复杂,技术要求高

接触网的运行环境和运行特点决定了接触网的结构较一般电力线路有很大的不同,为了保证电动车组安全、可靠、质量良好地从接触网取流,接触网的结构比较复杂,技术要求也比较高,如对接触网导线的高度、拉力值、定位器的坡度,接触网的弹性、均匀度等都有定量的要求。

4.3对接触网的基本要求

接触网的故障状态主要是指接触网与电动车组受电弓(或受流器)滑板的接触和导电情况。从电路要求上,为保证良好的导电情况,滑板与接触线的接触应保持一定的接触压力。在电动车组静止时,接触压力可以保持不变。当电动车组运行时,滑板跟着运动,与接触网形成滑动摩擦接触。这时,如能继续保持一定的接触压力,不间断的向电动车组供电,接触网才处于良好的跟着状态。因此,为了尽量保证对电动车组良好的供电,对接触网有一些基本的要求: (1). 接触网悬挂硬弹性均匀、高度一致,在高速行车和恶劣的气象条件下,能保证正常取流。

(2). 接触网结构应力求简单,并保证在施工和运营检修方面具有充分的可靠性和灵活性。

(3). 接触网的寿命应尽量长,具有足够的耐磨性和抗腐蚀能力。

(4). 接触网的建设应注意节约有色金属及其他车贵重材料,以降低成本。 4.4接触网的分类及其特点

接触网分为架空式接触网和接触轨式接触网(又称第三轨)。架空式接触网用于城市地面或地下、铁路干线、工矿的电力牵引线路。接触轨式接触网一般用于净空受限的地下电力牵引。我国在地铁轨道系统中,架空式和接触轨式均有采用。我国北京地铁采用的是接触轨式接触网,上海和广州均采用了架空式接触网。

4.4.1接触轨式馈电方式的特点

城市轨道交通的接触轨馈电方式中向车辆馈电的接触轨(根据集电靴和接触轨配合的方式,分为上磨式、上磨式和侧磨式等形式,如图4.1所示) 设置在车辆的走行轨旁。上磨式接触轨结构如图4.2所示,主要由接触轨、端部弯头、防爬器、隔离开关和防护罩等组成,并由绝缘子支撑。与之相配合,车辆采用集电靴受流。接触轨具有使用寿命长、维修量小、结构简单和运行费用低等优点,它能充分利用隧道空间,但接触轨系统距地面很近无法做到全方位的人员接近防护,在隧道内保养、检修或在车库内检修时应特别注意安全。

图4.1接触轨结构分类

图4.2 上磨式接触轨结构

另外某些城市车辆采用与上磨式接触轨配合的上磨式集电靴。在国内,北京地铁和城轨、天津地铁,在建的武汉城轨采用这种方式。上磨式集电靴这种方式一般适用于DC750V 电压供电,国外有个别城市有采DCl000V 电压供电而仍然使用接触轨馈电,并且车辆最高运行速度一般在90 km/h 以下。 4.4.2接触网馈电方式的特点

城市轨道交通的接触网馈电方式中向车辆馈电的接触网设置在车辆的走行轨上方,沿走行轨中心呈“之”字形走向,有柔性悬挂、弹性悬挂和刚性悬挂三种

方式,弹性悬挂和刚性悬挂方式只能用于隧道中。柔性悬挂方式的接触网采用全

补偿(正线) 或半补偿(站场或岔线) 简单链型悬挂,由接触导线、承力索、吊弦、导电连接线、辅助馈电线、绝缘子、坠坨和支持装置等构成;弹性悬挂则需要采用特制的专用弹性定位器,由接触导线、导电连接线、辅助馈电线、弹性定位器等构成;刚性悬挂方式的接触网则由接触导线、汇流排和绝缘子等构成。与之相配合,车辆采用受电弓受流。 (1)柔性悬挂。

这种悬挂形式不受线路位置的影响。在隧道内采用这种悬挂方式约需要500 mm 左右的安装空间,接触网张力约30 kN,全补偿。在国内,广州l 号线全线、上海地铁l 号线地面段、明珠线和在建的广州2号线地面段、深圳地铁全线和天津城轨滨海线采用了这种方式。地面上的接触网采用柔性悬挂形式。考虑到地面存在大气雷电的侵害, 因此随接触网架设有一条接地保护线, 并且在站场等重要场所增设避雷器。为了保证受电弓运行的连续性,通常在采用弹性悬挂和刚性悬挂接触网的隧道口设置一定距离的过渡段,然后再与柔性接触网连接。 (2)弹性悬挂

这种悬挂方式仅适用于隧道,需要采用一种悬挂专用的弹性定位器,接触网张力约1 5kN,半补偿。在国内,上海地铁1号线就在隧道中采用了弹性悬挂方式。采用这种方式需要约450 mm左右的安装空间。实验室内的单导线隧道简单弹性悬挂,对于城市轨道交通,这种悬挂方式通常采用双导线简单弹性悬挂。 (3)刚性悬挂。

这种悬挂方式同样仅适用于隧道。刚性悬挂实际上就是把第三轨放置在了隧道的顶部,安装高度约400 mm,但需要借助特殊的安装工具。在国内,广州地铁2号线中的地下线路将采用这种方式。

接触轨和接触网馈电方式的经济、技术综合性能比较见表4.3:

表4.3接触轨和接触网馈电方式的比较

5电力监控

在城市轨道交通系统中控制中心肩负着指挥中心和地铁运营的信息收发中心的使命。控制中心监控系统起着保证地铁全线安全运营和监视控制沿线信息的作用,其中设有电力监控,负责统一指挥全线供电设备运行。

5.1电力监控系统概述

电力监控SCADA (Supervisory Control And Data Acquisition)又称为远动监控和数据采集,主要用以实现对远方电力运行设备的监视和控制,以提高供电安全运行水平。

电力监控系统主要通过“四遥”实现其监控功能,即遥控、遥测、遥信和遥调。遥控是调度所对远方变电站被控对象(开关等)进行操作;遥测是将变电站被测对象的数值(电流、电压等)传送到调度所;遥信是将变电站被控对象(开关位置等)的状态信息传送到调度所;遥调是调度所对远方变电站工作状态和参数(变压器输出电压等)进行调整。另外电力监控系统还具有其他管理功能,例如报表管理、事故回放、故障分析、信息管理和技能培训等功能。

城市轨道交通电力监控系统采用分层分布式结构,即有调度控制中心、车辆段监控和供电复示系统、主变电所系统及车站变电所子站系统。

5.2沈阳地铁电力监控系统

沈阳地铁电力监控系统组成示意图5.2如下

图5.2沈阳地铁电力监控系统组成示意图

沈阳地铁一号线中央监控系统中控制中心选用DSC-9000U 自动化系统,其主要设备包括以太网交换机、系统服务器、web 服务器、打印服务器、操作员工作站、系统维护工作站、网络打印机以及网络连接附件等

变电所自动化综合系统采用国电南自NDT650自动化系统,其采用分层分布式结构,即站级管理层、网络通信层和间隔设备层。

站间管理层设备包括控制信号盘及盘内的通信交换机、交换机、一体化监控计算机;

网络通信层是两个独立的以太网接口,互为备用;

间隔管理层是分散安装于供电设备就地的微机保护测控、信息采集等装置。

结束语

供电系统是地铁所有用电用户的电能源泉,是机车和机电系统运行的动力保证。一旦供电系统发生故障,将使整条线路失去运营能力,造成重大经济损失。随着地铁线路的不断增多,地铁供电系统复杂程度越来越高,出现事故的可能性和故障波及的范围、造成的损失也不断增大。供电系统能否安全可靠运行将直接关系到地铁的安全、稳定运营,为了保证地铁安全可靠地运行,探讨其供电系统安全措施是极其有意义的。

本文通过分析城市轨道交通供电系统的各个组成部分,加深对地铁供电系统的了解,同时也加强了我本人搜集,整理、分析资料的能力,对我以后的工作、学习将产生极大的帮助。

【参考文献】

【1】 郑瞳炽,张明锐. 《城市轨道交通牵引供电系统》,中国铁道出版社,2009,22-88

【2】 张莹. 《工厂供配电技术》,电子工业出版社,2009,59-67

【3】 韩利民. 《地铁运营安全及对策研究》中国安全科学学报,2004,45~60

【4】 沈阳地铁岗前培训资料

【5】 徐安,陶生桂. 《城市轨道交通电力牵引》,中国铁道出版社,2000.3,90~112

【6】 孙有望,李云清. 《城市轨道交通概论》,中国铁道出版社,2008.8,3~25


相关内容

  • 城市轨道交通安全验收评价细则
  • 城市轨道交通安全验收评价细则 1范围 本标准规定了城市轨道交通安全验收评价的程序.内容等基本要求,以及城市轨道交通安全验收评价报告的编制格式. 本标准适用于国内城市轨道交通的安全验收评价工作. 2规范性引用文件 下列标准所包含的条文,通过在本标准中引用而构成本标准的条文.本标准出版时,所示版本均为有 ...

  • 建筑节能论文[城市轨道交通工程节能技术与策略浅论]
  • 城市轨道交通节能技术与实施策略浅论 冯西培 (北京城建设计发展集团股份有限公司北京 100037) 摘要:能源是发展国民经济.改善人民生活的重要物质基础.能源的紧张,将严重阻碍人们未来的正常生活.社会进步和经济的可持续发展,人类的现代文明将付诸东流.结合城市轨道交通能耗特点与实施节能的背景,并提出节 ...

  • 城市轨道交通信息通信系统技术分析
  • 摘要: 本文从我国城市轨道交通信息通讯系统的研究现状出发,主要分析了系统的核心技术,以期城市轨道交通信息通信系统能够充分发挥其在轨道建设中的作用. Abstract: Starting from the research status of the information communication ...

  • (完整版)城市轨道交通毕业论文
  • 哈尔滨铁道职业技术学院 毕 论文题目 学生姓名 专业班级 业 论 文 城市轨道交通运营安全管理模式的研究 指导教师 城市轨道交通学院 年 月 日 安全管理 摘 要 城市轨道交通运营专业性强.技术设备复杂.客流量大,造成城市 轨道交通安全运营管理的难度较大,因而建立城市轨道交通运营安全管理模式,预防事 ...

  • (完整版)城市轨道交通毕业论文设计
  • 哈尔滨铁道职业技术学院 毕 业 论 文 论文题目 城市轨道交通运营安全管理模式的研究 学生姓名 专业班级 指导教师 城市轨道交通学院 年 月 日 安全管理 摘 要 城市轨道交通运营专业性强.技术设备复杂.客流量大,造成城市 轨道交通安全运营管理的难度较大,因而建立城市轨道交通运营安全管理模式,预防事 ...

  • 城市轨道交通发展现状及未来趋势
  • 国向外城市轨道交通的现状与发展趋势 摘要: 随着我国城市化和机动化进程的加快,交通拥堵问题已成为当前我国各大城市发展的"瓶颈".如不能有效地解决城市交通问题.将严重影响大城市的可持续发展.但是,解决大城市交通问题要有前瞻性,要结合我国国情以及各大城市自身特点来确定大城市交通的发展 ...

  • 城市轨道交通工程技术发展和管理的认识与思考
  • 城市轨道交通工程技术发展和管理的认识与思考 摘要:论文对城市轨道交通工程建设现状与发展趋势进行了粗浅的分析,论述了城市轨道交通应该坚持工程建设统筹化.区域化.国产化.信息智能化和环保节能化的发展方向,并应积极推进技术与管理创新.同时,城市轨道交通工程技术的发展要求必须加强工程建设管理手段的综合运用与 ...

  • 上海城市轨道交通网络建设与资源共享
  • 第6期 百家论坛 上海城市轨道交通网络建设与资源共享 顾伟华 (上海申通地铁集团有限公司, 200031, 上海M 教授级高级工程师, 副总裁) 摘 要 介绍了上海城市轨道交通建设的现状和近.远期的发展规划.鉴于国外城市轨道交通发展的经验和上海城市轨道交通即将成网的现实, 就人力.土地.运营设备与设 ...

  • 我国城市轨道交通技术装备发展水平与制造能力
  • 第10期 百家论坛 我国城市轨道交通技术装备发展水平与制造能力 周翊民 (中国交通运输协会城市轨道交通专业委员会,100844,北京M副主任,教授级高级工程师) 摘 要 介绍了我国城市轨道交通技术装备的基础标准和城市轨道交通类型选择标准.论述了我国城市轨道交通在车辆.信号.检票和安全系统设备方面的最 ...

  • [城市轨道交通概论]教案
  • <城市轨道交通概论> 教 案 陈 璇 二零一四年九月 第一章 城市轨道交通及其发展 任务一 城市轨道交通认知 一.轨道交通的定义 根据轨道交通的特性,从广义上讲,凡是车辆运行在导轨上的交通运输工具都可称为轨道交通运输.在轨道交通运输发展的历史进程中,人们常把担当长大运输的铁路称为大铁路( ...