临时用电方案以审批

XXXX 安置小区4栋

临 时 用 电 施 工 方 案

目 录

第一章 编制依据 ..........................................................................................................................3 第二章 工程概况 ..........................................................................................................................3 第二章 施工用电部署 ...................................................................................................................3

一、本工程所需主要施工用电设备:...........................................................................................3

二、临时用电规划: ...................................................................................................................5 三、工作零线和保护零线:.........................................................................................................5 四、配电箱 .................................................................................................................................6 五、配电线路..............................................................................................................................6 六、现场勘探及线路走向 ............................................................................................................7 七、级电箱位置及布线原则: .....................................................................................................7 第三章 施工用电计算 ...................................................................................................................8

一、施工用电计算说明: ............................................................................................................8 二、施工用电总容量计算:.........................................................................................................8 三、所需变压器容量:................................................................................................................8 四、用电管理措施: ...................................................................................................................9 五、按工作电流选择配电导线截面:(主线) ..............................................................................9 第四章 安全用电技术措施和电气防火措施.................................................................................. 10 一、技术措施: ........................................................................................................................ 10 二、防火措施............................................................................................................................ 15 第五章 施工现场用电平面布置图................................................................................................ 16 第六章 施工现场临时用电管理制度 ............................................................................................ 16

一、电气维护制度..................................................................................................................... 16

二、工作监护制度..................................................................................................................... 16 三、安全用电技术交底制度....................................................................................................... 17 四、安全检测制度..................................................................................................................... 17 五、电工及用电人员的操作制度................................................................................................ 17 第七章 应急措施 ........................................................................................................................ 18 第八章 施工现场用电管理机构设置 ............................................................................................ 19

第一章 编制依据

本方案的编制依据为:

1、本工程拟采用主要用电设备汇总;

2、《施工现场临时用电安全技术规范》(JGJ46-2005); 3、现场总平面布置。

第二章 工程概况

本工程位于XXXXX ,砖混结构,6F+1F,占地总面积1050m 2,总建筑面积7750.59余平方米,建筑高度21.300m (室外至屋面面层)。;

抗震设防烈度为六度,耐火等级为二级;基础为人工挖孔桩基础。

第二章 施工用电部署

一、本工程所需主要施工用电设备:

本工程由1栋建筑构成, 考虑到本工程的工期短,建筑单层建筑面积大,为了顺利完成本工程,我们拟采用一台QTZ63塔吊做为该工程的主体垂直运输设备,工程混凝土施工采用自拌混凝土塔吊运输转运施工,共布置1个钢筋加工车间、1个木工车间。1个混凝土搅拌场,临时用电平面布置详见《施工用电平面布置图》。

本工程拟采用主要用电设备表

二、临时用电规划:

1、根据现场施工分区和机电设备的安排,进行主要用电设备安排:

Ⅰ主要用电设备用电统计表

2、施工现场临时用电按照建设部颁布的《施工现场临时用电安全技术规范》(JGJ46-2005)中的规定进行实施。

3、根据现场勘测确定电缆走向,根据现场施工用电情况,绘制《施工用电平面布置图》,作为临时用电依据。

4、“三相五线制”供电系统:施工现场专用的中性点直接接地的电力线路必须采用TN-S 接零保护系统。

三、工作零线和保护零线:

1、保护零线应由工作接地线处引出;

2、保护零线严禁穿过漏电保护器;工作零线必须穿过漏电保护器; 3、电箱中应设置两块端子板;

4、保护零线必须重复接地,工作零线禁止接地。 四、配电箱

1、“三级配电两级保护”:用电线路必须经过一级配电柜→二级配电箱→三级配电箱→用电设备;保护系统在末级开关箱内加装漏电保护器。

2、采用“一机一闸一漏电”制。 3、电箱的安装位置

3.1总配电箱设置见《施工用电平面布置图》。

3.2分配电箱设置在用电设备或负荷相对集中的地区,二级配电箱与三级配电箱的距离一般情况不得大于30m ,三级配电箱与其控制的固定式用电设备的水平距离不得超过3m 。

3.3固定式配电箱、开关箱的中心点与地面的垂直距离为1.4m ~1.6m 。移动式配电箱、开关箱的中心点与地面的垂直距离宜为0.8m ~1.6m 。

4、所有配电箱都必须配锁。

五、配电线路

1、所有电缆必须采用五芯电缆,导线采用绝缘铜导线。

2、从建设方配电室至配电房采用埋地电缆,配电房至施工现场采用架空敷设,电杆间距25m ~30m ,架空高度大于5m 。

3、电缆垂直敷设的位置利用在建工程垂直孔洞,并在靠近用电负荷中心设置分配电箱或开关箱。固定点每层楼不得少于一处。在建筑屋内电缆水平敷设沿墙或门口固定。

4、紧电缆用的铁丝或钢丝绳应能承受全部拉力,与电缆线连接必须牢固。紧线时导线下方不得站人。终端紧线时反方向应设置临时拉线。

5、电缆干线采用埋地或架空敷设,严禁沿地面明敷设,并应避免机械损伤和介质腐蚀。

6、电缆在室外直接埋地敷设时,必须按电缆埋设图敷设,并应砌砖槽防护,

埋设深度不得小于0.7m.

7、电缆的上下各均匀铺设不小于5cm 厚的细砂,上盖电缆盖板或红机砖作为电缆的保护层。

8、地面上应有埋设电缆的标志,并应有专人负责管理。不得将物料堆放在电缆埋设的上方。

9、有接头的电缆不准埋在地下,接头处应露出地面,并配有电缆接线盒。电缆接线盒应防雨、防尘、防机械损伤,并远离易燃、易爆、易腐蚀场所。

10、电缆穿越建筑物、构筑物、道路、易受机械损伤的场所及引出地面从2m 高度至地下0.2m 处,必须加设防护套管。

11、电缆线路与其附近热力管道的平行间距不得小于2m ,交叉间距不得小于1m 。

六、现场勘探及线路走向

现场主是由甲方提供的变压器接入现场所修的配电房,提供电压为380/V,总容量为500kW, 根据施工现场建筑特点和临时用电设备布设,按现场施工临时用电布置图,施工临时用电从配电房用电缆架空引出(或埋地), 引至现场一级配电柜(施工配电房)处, 再由一级配电柜分出塔吊、钢筋加工车间、木工车间、其他小型设备施工用电、生活及照明用电专用。

七、级电箱位置及布线原则:

(1)塔吊配电箱设在基础边,便于电源进出线。

(2)钢筋加工配电箱设在钢筋加工棚处,采用埋地敷线,以便材料进场。 (3)振捣器配电箱应布置在使用地点附近(即流动电箱)。

(4)砂浆机、灰机的配电箱设在砂场及灰池附近,导线采用架空敷设。 (5)电焊机为可移动设备,采用回路供电,导线采用橡皮套软电缆。 (6)分配电箱距固定式用电设备距离均不超过3米,距交流弧焊机距离不大于5米。

第三章 施工用电计算

一、施工用电计算说明:

本工程在人工挖孔桩施工完毕后,大部分空压机、潜水泵需出场,施工用电配电容量不考虑空压机与潜水泵的施工用电。本计算只考虑用电主干线。

二、施工用电总容量计算:

本工程孔桩施工完毕后,大部分空压机、潜水泵和打夯机需出场,配电容量不考虑空压机、潜水泵、打夯机的施工用电。

1、电动机功率:

∑P =塔吊电动机功率+井架电动机功率+钢筋加工机械电动机功率

+砂浆机电动机功率=50+25+72.52+15=162.5(KW)

2、电焊机容量

∑P 1=93.6(KWA)

3、动力用电容量:

P动= K1×∑P 1÷cos φ+ K2×∑P 2

=0.6×509.4÷0.7+0.6×93.6=361.8(KVA) 4、照明用电容量:

考虑本工程工期紧,夜间施工较多,取动力用电容量的15%。 P照=0.15 P动=0.15×361.8=54.27(KVA) 5、用电总容量为:

∑P 总= P动+ P照=361.8+54.27=416.07(KVA)

三、所需变压器容量:

W=K×∑P 总÷ cosφ=1.05×416.07÷0.75=582.498(KVA) 式中说明:K=功率损失系数。

业主提供的电源变压器容量为600KVA ,能满足施工最大用电高峰要求。 变压器到配电房采用150mm 2绝缘铝芯橡皮导线。

四、用电管理措施:

为此,采取用电分配控制措施,使用主要的大功率用电设备分时间段错开使用,避免用电出现最高峰以导致变压器受损。 五、按工作电流选择配电导线截面:(主线)

1、Ⅰ路工作电流: 1.1动力部分:

I动力 =K1×∑P ÷(√3×V ×cos φ)

={0.6×[215.8+(0.6×46.8)]×1000}÷[√3×380×0.75] =296.43(A)

1.2照明部分:

I照明 =0.15×I 动力=0.15×296.43=44.46(A) 1.3工作电流:

I工作电流= I动力+ I照明=296.43+44.46=340.89(A) 1.4导线截面选择:

查表选用150mm 2的绝缘铝芯橡皮导线。 2、Ⅱ路工作电流: 2.1动力部分:

IⅡ路动力 =K1×∑P ÷(√3×V ×cos φ)

={0.6×[226.8+(0.6×46.8)]×1000}÷[√3×380×0.75] =309.81(A)

2.2照明部分:

IⅡ路照明 =0.15×I Ⅱ路动力=0.15×309.81=46.47(A) 2.3工作电流:

IⅡ路工作电流= IⅡ路动力+ IⅡ路照明=309.81+46.47=356.28(A) 2.4导线截面选择:

查表选用150mm 绝缘铝芯橡皮导线。

2

第四章 安全用电技术措施和电气防火措施

一、技术措施:

1、施工现场配有专业电工一名负责施工现场临时用电(持证上岗)。 2、配电房:

2.1配电房门向外开,并上锁,严禁无关人员进入,不准堆放任何杂物,配置两台干粉灭火器。

2.2供电系统采用三相五线制,漏电保护器和空气开关的选择执行国家标准。

2.3配电盘正面的操作通道宽不小于1.5m, 背面的维护通道宽不小于0.8m 。 2.4配电盘应设短路、过负荷保护装置和漏电保护器,配电盘上的各配电线路排列整齐,标记齐全清楚,并标明用途。

2.5配电盘和配电线路维修时,应悬挂停电标志牌,停、送电必须由持证专业电工负责。送电时必须先合隔离开关,后合空气开关或漏电断路器;停电操作顺序相反。

2.6总配电箱中漏电保护器的额定漏电动作电流应大于150mA ,额定漏电动作时间应大于0.2S ,但其额定漏电动作电流与额定漏电动作时间的乘积不应大于30mA ·s 。

3、配电线路:

引入和引出电缆干线采用埋地敷设,埋地深度为0.7m ,埋置于环境干燥且无介质腐蚀。

室内配线采用绝缘导线,用塑料卡敷设,距地面高度不得小于2.5m, 铜线截面不得小于1.5mm 2。

4、配电箱及开关箱:

4.1配电系统设置室内总配电屏和室外总配电箱、分配电箱,实行分级配电。室内总配电屏动力和照明线路分路设置,开关箱由末级分配电箱配电。

4.2配电箱、开关箱设在干燥、通风及常温场所,不得有灌木和杂草, 其周围应有足够二人同时工作的空间和通道,并不得堆放任何防碍操作、维修的物品。

4.3配电箱、开关箱应装设端正、牢固,移动式配电箱、开关箱装设在坚固的支架上,配电箱、开关箱内的电器必须可靠完好,不准使用破损、不合格的电

器。

4.4分配电箱应装设总隔离开关和分路隔离开关以及总熔断器和分路熔断器。总开关电器的额定值、动作整定值应与分路开关电器的额定值、动作整定值相适应。

4.5每台用电设备设置各自专用的开关箱,实行“一机一闸”制,严禁同一个开关电器直接控制二台及二台以上的用电设备。

4.6开关箱中必须装设漏电保护器,漏电保护器装设在负荷线的首端处。

4.7漏电保护电器应装设在配电箱电源隔离开关的负荷侧,漏电保护电器的选择应符合国标GB6829-86《漏电电流动作保护器(剩余电流动作保护器)》的要求,开关箱内的漏电保护电器其额定漏电动作电流不大于30mA ,额定漏电动作时间不大于0.1S ,

4.8配电箱、开关箱中导线的进线口和出线口应设在箱体的下底面,严禁设在箱体的上顶面、侧面、后面或箱门处,导线束不得与箱体进出口直接接触。移动式配电箱、开关箱的进、出线必须采用橡皮绝缘电缆。

4.9所有配电箱、开关箱应每月检查一次,检查、维修时必须由专业电工按规定穿、戴绝缘鞋、手套,必须使用电工绝缘工具。

5、电动建筑机械和手持电动工具:

5.1施工现场一切电动建筑机械和手持电动工具的选购、使用、检查和维修必须遵守下列规定:

5.1.1选购的电动建筑机械、手持电动工具和用电安全装置,应符合相应的国家标准、专业标准和安全技术规程,并且有产品合格证和使用说明书。

5.1.2建立和执行专人专机负责制,并定期检查和维修保养。

5.1.3保护零线的电气连接和漏电保护器按规范设置,保护接地线严禁作为零线使用。

5.1.4楼层上每隔两层设置施工配电箱,配电箱之间配电电缆采用橡套电缆穿PVC 管明配,施工用具振动器、电焊机等电源线采用橡套电缆,保护接地可靠,漏电保护开关动作灵敏,不能带电移动施工用具,特殊设备振动器使用过程中移动时不允许强行拖拉电源线,必须另外有人员帮助移动电缆。

5.1.5在施工现场的工具和材料不允许堆放电线电缆上,现场人员不允许在

电线电缆上踩踏。

5.1.6现场施工用水管要和配电箱及电线电缆保持一定的距离,防止水飞溅到配电设备和用电设备上;施工完毕后用电设备进线端必须断电,用电设备和配电箱要经常覆盖,防止下雨淋湿。

5.2夯土机械:

5.2.1夯土机械开关箱中的漏电保护器额定漏电动作电流不得大于30mA ,额定漏电动作时间不大于0.1S ;

5.2.2夯土机械PE 线的连接点不得小于2处;

5.2.3夯土机械的负荷采用耐气候型橡皮护套铜芯软电缆;

5.2.4使用夯土机械按规定穿戴绝缘用品,使用过程派专人调整电缆,电缆长度不大于50m 。电缆严禁缠绕、扭结和被夯土机械跨越;

5.2.5夯土机械的操作扶手必须绝缘。

5.3起重机械(塔吊、物料提升机):

5.3.1塔吊的电气设备符合《塔式起重机安全规程》GB5144的要求;

5.3.2塔吊的电气设备所连接PE 线必须同时做重复接地,重复接地和防雷接地可共用同一接地体,但接地电阻应符合重复接地电阻值的要求;

5.3.3物料提升机的上下极限位置设置限位开关;

5.3.4每日工作前必须对行程开关、限位开关、紧急停止开关、驱动机械和制动器等进行空载检查,正常后方可使用。检查时必须有防坠落措施。

5.4焊接机械:

5.4.1电焊机放置在防雨、干燥和通风良好的地方;焊接现场不得有易燃、易爆物品;

5.4.2交流弧焊机变压器的一次侧电源线长度不大于5m ,其电源进线必须设置防护罩。

5.4.3电焊机械开关箱中的漏电保护器额定漏电动作电流不应大于30mA ,额定漏电动作时间不应大于0.1S 。

5.4.4电焊机械的二次线应采用防水橡皮护套铜芯软电缆,电缆的长度不应大于30m ,不得采用金属构件或结构钢筋代替二次线的地线。

5.4.5使用电焊机械焊接时必须穿戴防护用品,严禁露天冒雨从事电焊作

业。

6、手持式电动工具:

6.1空气温度小于75%的一般场所可先用Ⅰ类或Ⅱ类手持式电动工具,其金属外壳与PE 线的连接点不得小于2处;除塑料外壳Ⅱ类工具外,相关开关箱中漏电保护器的额定漏电动作电流不应大于15mA ,额定漏电动作时间不应大于0.1S ,其负荷线插头应具备专用的保护触头。所用插座和插头在结构上应保护一致,避免导电触头和保护触头混用。

6.2在潮湿场所或金属构架上操作时,必须选用Ⅱ类或由安全隔离变压器供电的Ⅲ类手持式电动工具。金属外壳Ⅱ类手持式电动工具使用时,必须符合6.1条要求;其开关箱和控制箱应设置在作业场所外面。在潮湿场所或金属构架上严禁使用Ⅰ类手持式电动工具。

6.3狭窄场所必须选用由安全隔离变压器供电的Ⅲ类手持式电动工具,其开关箱和安全隔离变压器均应设置在狭窄场所外面,并连接PE 线。漏电保护器的额定漏电动作电流不应大于15mA ,额定漏电动作时间不应大于0.1S 。

6.4手持式电动工具的负荷线应采用耐气候型的橡皮护套铜芯软电缆,并不得有接头。

6.5手持式电动工具的外壳、手柄、插头、开关、负荷线等必须完好无损,使用前必须做绝缘检查和空载检查,在绝缘合格、空载运转正常后方可使用。

6.6使用手持式电动工具时,必须按规定穿、戴绝缘防护用品。

7、照明:

7.1照明器具和器材的质量均应符合有关标准、规范的规定,不得使用绝缘老化或破损的器具和器材。

7.2照明系统的每一个单相回路上,灯具和插座数量不得超过25个,并应装设熔断电流为15A 及15A 以下的熔断器保护。

7.3照明灯具金属外壳必须作保护接零,室外灯具距地面不得低于3m ,室内灯具不得低于2.4m 。

7.4电器、灯具的相线必须经开关控制,不得将相线直接引入灯具。

8、接地和防雷:

8.1施工现场采用TN -S接零保护系统。电气设备的金属外壳必须与专用的

保护零线连接。

8.2施工现场严禁利用大地作为相线或零线,保护零线不得装设开关或熔断器。

8.3保护零线单独设置,不作它用。重复接地应与保护零线相连接,与电气设备相连接的保护零线应为截面不小于2.5mm 的绝缘多股铜线。

8.4正常情况下,下列电气设备不带电的外露导电部分应接地:

8.4.1电机、电器、照明器具、手持电动工具的金属外壳。

8.4.2电气设备传动装置的金属部件。

8.4.3配电屏和控制屏的金属框架。

8.4.4室内外配电装置的金属框架及靠近带电部分的金属围栏和金属门。

8.5塔吊利用桩基作为重复接地,接地可靠, 接地电阻小于1Ω。

9、工地的一切用电设备必须由电工接线和管理,不得擅自架设和装电路,电工必须持证上岗,严禁违章操作。

10、电工在接线、电气设备安装时,应按照施工设计和有关电气安全技术规程进行作业,应正确使用绝缘防护用品和经定期检查校验的绝缘检验工具。电气操作人员严格执行电工操作规程。

11、电缆架空敷设时,应沿墙壁或电杆设置,并和绝缘子固定,严禁用金属裸线作绑线,室外架空高度不小于3M ,室内不小于2.5M 。水平沿墙敷放或门口固定最低点不得小于1.8M 。

12、电工人员严禁带电操作,线路上禁止带负荷接线,正确使用电工器具。

13、电气设备的金属外壳必须做接地、接零保护。

14、电气设备所用保险丝,禁止用其它金属丝代替,并且需与设备容量相匹配。凡移动式照明,必须采用安全电压。

15、施工现场临时用电施工,必须执行施工组织设计和安全操作规程。

16、开机前认真检查开关箱内的控制开关设备是否齐全有效,漏电保护器是否可靠,方能使用。严禁赤手触摸一切带电绝缘导线。

17、下班后1小时必须把总电制关好并把电箱门锁上。

18、电工必须定期检查所有漏电开关是否正常,并认真登记安全生产检查记录。 2

19、开关箱距操作者的水平距离不超过3米,按钮开关不能安装在交流接触器一侧。

20、开关箱内禁止放任何杂物,箱不能堆放沙子、水泥、白灰、水泥袋等,且灌木、杂草要清除干净。

21、开关箱安装距地面高度为1.3M-1.5M ,且安装牢固,要具有防尘、防雨功能。

22、开关箱必须完整无缺,并配上锁,锁匙由专人保管。

23、开关箱必须有当心触电的标志。

24、三级漏电保护开关的额定漏电动作电流应不大于30mA ,额定漏电动作时间应小于0.1S 。

25、其余规定参照《施工现场临时用电安全技术规范》JGJ46-2005。

二、防火措施

1、合理配置用电系统的短路、过载、漏电保护电器;

2、确保PE 线连接点的电气连接可靠;

3、在电气设备和线路周围不堆放并清除易燃易爆物和腐蚀介质,并作阻燃隔离防护;

4、不在电气设备周围使用火源,特别在配电室、配电箱等场所严禁烟火;

5、在电气设备相对集中场(配电室、钢筋加工车间、木工车间等)配置干砂、干粉灭火器,禁止使用灭火剂灭火;

6、建立电气防火责任制,加强电气防火重点场所烟火管制,并设置禁止烟火标志;

7、建立电气防火教育制度,定期进行电气防火知识宣传教育,提高现场各工种和人员电气防火意识和电气防火知识水平;

8、建立电气防火检查制度,发现问题,及时处理,不留任何隐患;

9、电焊作业时须配置灭火器,并派专人监护,作业完毕,留有充分的时间观察,确认无引火点后,方可离去;

10、施工现场焊、割作业前执行“动火证制度”,并切实做到用火有措施,灭火有准备;

第五章 施工现场用电平面布置图

见附图

第六章 施工现场临时用电管理制度

一、电气维护制度

1、只准全部(操作范围内)停电工作、部分停电工作,不准进行不停电工作。维修工作要严格执行电气安全操作规程。

2、不准私自维修不了解内部原理的设备和装置。不准私自维修厂家禁修的安全保护装置。不准私自超越指定范围进行维修作业。不准从事超越自身技术水平且无指导人员在场的电气维修作业。

3、不准在本单位不能控制的线路及设备上工作。

4、不准随意变更维修方案而使隐患扩大。

5、不准酒后或有过激行为之后进行维修作业。

6、对施工现场所属的各类电动机,每年必须清扫、注油或检修一次。对变压器、电焊机,每半年必须进行清扫或检修一次。对一般低压电器、开关等,每半年检修一次。

二、工作监护制度

1、在带电设备附近工作时必须设人监护。

2、在狭窄及潮湿场所从事用电作业时必须设专人监护。

3、登高用电作业时必须设专人监护。

4、监护人员应时刻注意工作人员的活动范围,督促其正确使用工具,并与带电设备保持客观存在全距离。发现违反电气安全规程的作法应及时纠正。

5、监护人员的安全知识及操作技术水平不得低于操作人。

6、监护人员在执行监护工作时,应根据被监护工作情况携带或使用基本安全用具或辅助安全用具,不得兼做其他工作。

三、安全用电技术交底制度

1、进行临时用电工程的安全技术交底,必须分部分项且按进度进行。不准一次性完成全部工程交底工作。

2、设有监护人的场所,必须在作业前对全体人员进行技术交底。

3、对电气设备的试验、检测、调试前、检修前及检修后的通电试验前,必须进行技术交底。

4、支电气设备的业期维修前、检查后的整改前,必须进行技术交底。

5、交底项目必须齐全,包括使用的劳动保护用品及工具,有关法规内容,有关安全操作规程内容和保证工程质量的要求,以及作业人员活动范围和注意事项等。

6、填写交底记录要层次清晰,交底人、被交底人及交底负责人必须分别签字,并准确注明交底时间。

四、安全检测制度

1、测试工作接地电阻和防雷接地电阻值,必须每年在雨季前进行。

2、测试重复接地电阻值必须每季至少进行一次。

3、更换和大修设备或每移动一次设备,应测试一次电阻值。测试接地电阻值工作前必须切断电源,断开设备接地端。操作时不得少于两人,禁止在雷雨时及降雨后测试。

4、必须对漏电保护器进行一次主要参数的检测,不符合铭牌值范围时应立即更换或维修。

5、对电气设备及线路、施工机械电动机的绝缘电阻值,每年至少检测两次。摇测绝缘电阻值,必须使用与被测设备、设施绝缘等相适应的(按安全规程执行)绝缘摇表。

6、检测绝缘电阻前必须切断电源,至少两人操作。禁止在雷雨时摇测大型设备和线路的绝缘电阻值。检测大型感性和容性设备前后,必须按规定方法放电。

五、电工及用电人员的操作制度

1、禁止使用或安装木质配电箱、开关箱、移动箱。电动施工机械必须实行

“一机一闸一漏一箱”。且开关箱与所控固定机械之间的距离不得大于5M 。

2、严禁以取下(给上)熔断器方式对线路停(送)电。严禁维修时约时送电,严禁以三相电源插头代替负荷开关启动(停止)电动机运行。严禁使用220V 电压行灯。

3、严禁频繁按动漏电保护器和私拆漏电保护器。

4、严禁长时间超铭牌额定值运行电气设备。

5、严禁在同一配电系统中一部分设备作保护接零,另一部分设备作保护接地。

6、严禁直接使用刀闸启动(停止)4KW 以上电动设备。严禁直接在刀闸上或熔断器上挂接负荷线。

第七章 应急措施

一、触电事故应急措施:

1、现场人员应当机立断地脱离电源,尽可能的立即切断电源(关闭电路),亦可用现场得到的绝缘材料等器材使触电人员脱离带电体。

2、将伤员立即脱离危险地方,组织人员进行抢救。

3、若发现触电者呼吸或呼吸心跳均停止,则将伤员仰卧在平地上或平板上立即进行人员呼吸或同时进行体外心脏按压。

4、立即拨打120向当地急救中心取得联系(医院在附近的直接送往医院),应详细说明事故地点、严重程度、本部门的联系电话,并派人到路口接应。

5、立即向公司应急抢救领导小组汇报事故发生情况并寻求支持。

6、维护现场秩序,严密保护事故现场。

二、应急物资

常备药品:消毒用品、急救物品(绷带、无菌敷料)及各种常用小夹板、担架、止血袋、氧气袋。

三、注意事项

1、在末脱离电源时,切不可用手去拉触电者。

2、事故发生时应组织人员进行全力抢救,视情况拨打120急救和马上通知有关负责人。

3、注意保护好事故现场,便于调查分析事故原因。

4、心肺复苏抢救措施要坚持不断的进行(包括送医院的途中)不能随便放弃。

第八章 施工现场用电管理机构设置

一、施工现场用电安全领导小组:

成立以项目经理为首的“惠水县高镇安置小区工程项目安全领导小组”,组织机构如下:

二、管理措施:

1、用电安全检查制度:

严格监督检查,消除事故隐患。用电安全领导小组每周定期对项目进行检查;专职电工、机电员和安全员坚持每日安全巡视。对检查发现的事故隐患,定人、定时间、定措施进行整改,不留事故隐患。机械设备、施工用电、防护设施等要经验收合格后才能投入使用。每次检查后,由安全员作好记录,归入档案。

2、班前安全活动:

开工前,必须由安全员及班组长对工人进行安全技术交底,并履行签字手续。活动后由安全员作安全教育活动记录。

3、安全教育:

3.1日常教育:广泛开展安全生产的宣传教育,在工人进场和施工全过程中,对全体施工人员进行安全思想教育、施工安全知识教育,使施工人员真正认识到

安全生产的重要性和必要性,提高施工人员的安全意识和安全生产素质,为安全生产打好基础。

3.2安全纪律教育:使施工人员了解安全生产规章制度、安全生产责任制、安全生产劳动纪律、安全生产奖惩条例,增强全员的安全生产法制意识,使其能自觉遵守各项安全生产法令和规章制度。

3.3安全技术教育:对各岗位操作人员进行本岗安全生产知识和技术教育;对特殊岗位操作人员进行培训,考核合格后持证上岗。

3.4班前安全交底:班前对工人进行简洁而明确的安全、技术交底和动员,并交代好操作事项,班后要对当日的安全生产状况进行讲评,改进措施,总结经验。

3.5 操作工艺交底:由项目技术主管保证工程的操作工艺无安全缺陷,并负责将操作工艺向具体施工人员交底,交底以书面形式进行,以使操作人员对操作的危险性和防卫措施有充分的了解。

三、工地消防管理:

1、成立以项目经理为组长的现场消防小组,负责消防管理。

2、消防小组人员定期进行消防检查。

3、保证消防道路畅通,有明显防火标志和防水制度牌,消防设施器具,足够合格有效,消防器材不得随便动用。

4、施工材料按防火安全要求存放,保管易燃、易爆材料专库储存,库房按防火要求和火等级搭建,易燃、易爆剧毒物品单独存放严格控制。

5、特殊工种持证上岗,电气焊工明火作业要有用火证,派专人负责并配灭火器,禁止违章作业。

6、做好成品保护,防止破坏行为,发生火灾及进报警。

7、冬季施工使用电热器,须符合安全规范,并经消防负责人同意,冬季施工用保温材料,不得采用可燃材料。

8、施工中使用化学易燃物器时,禁止交叉作业和作业场所分装,调料。

XXXX 安置小区4栋

临 时 用 电 施 工 方 案

目 录

第一章 编制依据 ..........................................................................................................................3 第二章 工程概况 ..........................................................................................................................3 第二章 施工用电部署 ...................................................................................................................3

一、本工程所需主要施工用电设备:...........................................................................................3

二、临时用电规划: ...................................................................................................................5 三、工作零线和保护零线:.........................................................................................................5 四、配电箱 .................................................................................................................................6 五、配电线路..............................................................................................................................6 六、现场勘探及线路走向 ............................................................................................................7 七、级电箱位置及布线原则: .....................................................................................................7 第三章 施工用电计算 ...................................................................................................................8

一、施工用电计算说明: ............................................................................................................8 二、施工用电总容量计算:.........................................................................................................8 三、所需变压器容量:................................................................................................................8 四、用电管理措施: ...................................................................................................................9 五、按工作电流选择配电导线截面:(主线) ..............................................................................9 第四章 安全用电技术措施和电气防火措施.................................................................................. 10 一、技术措施: ........................................................................................................................ 10 二、防火措施............................................................................................................................ 15 第五章 施工现场用电平面布置图................................................................................................ 16 第六章 施工现场临时用电管理制度 ............................................................................................ 16

一、电气维护制度..................................................................................................................... 16

二、工作监护制度..................................................................................................................... 16 三、安全用电技术交底制度....................................................................................................... 17 四、安全检测制度..................................................................................................................... 17 五、电工及用电人员的操作制度................................................................................................ 17 第七章 应急措施 ........................................................................................................................ 18 第八章 施工现场用电管理机构设置 ............................................................................................ 19

第一章 编制依据

本方案的编制依据为:

1、本工程拟采用主要用电设备汇总;

2、《施工现场临时用电安全技术规范》(JGJ46-2005); 3、现场总平面布置。

第二章 工程概况

本工程位于XXXXX ,砖混结构,6F+1F,占地总面积1050m 2,总建筑面积7750.59余平方米,建筑高度21.300m (室外至屋面面层)。;

抗震设防烈度为六度,耐火等级为二级;基础为人工挖孔桩基础。

第二章 施工用电部署

一、本工程所需主要施工用电设备:

本工程由1栋建筑构成, 考虑到本工程的工期短,建筑单层建筑面积大,为了顺利完成本工程,我们拟采用一台QTZ63塔吊做为该工程的主体垂直运输设备,工程混凝土施工采用自拌混凝土塔吊运输转运施工,共布置1个钢筋加工车间、1个木工车间。1个混凝土搅拌场,临时用电平面布置详见《施工用电平面布置图》。

本工程拟采用主要用电设备表

二、临时用电规划:

1、根据现场施工分区和机电设备的安排,进行主要用电设备安排:

Ⅰ主要用电设备用电统计表

2、施工现场临时用电按照建设部颁布的《施工现场临时用电安全技术规范》(JGJ46-2005)中的规定进行实施。

3、根据现场勘测确定电缆走向,根据现场施工用电情况,绘制《施工用电平面布置图》,作为临时用电依据。

4、“三相五线制”供电系统:施工现场专用的中性点直接接地的电力线路必须采用TN-S 接零保护系统。

三、工作零线和保护零线:

1、保护零线应由工作接地线处引出;

2、保护零线严禁穿过漏电保护器;工作零线必须穿过漏电保护器; 3、电箱中应设置两块端子板;

4、保护零线必须重复接地,工作零线禁止接地。 四、配电箱

1、“三级配电两级保护”:用电线路必须经过一级配电柜→二级配电箱→三级配电箱→用电设备;保护系统在末级开关箱内加装漏电保护器。

2、采用“一机一闸一漏电”制。 3、电箱的安装位置

3.1总配电箱设置见《施工用电平面布置图》。

3.2分配电箱设置在用电设备或负荷相对集中的地区,二级配电箱与三级配电箱的距离一般情况不得大于30m ,三级配电箱与其控制的固定式用电设备的水平距离不得超过3m 。

3.3固定式配电箱、开关箱的中心点与地面的垂直距离为1.4m ~1.6m 。移动式配电箱、开关箱的中心点与地面的垂直距离宜为0.8m ~1.6m 。

4、所有配电箱都必须配锁。

五、配电线路

1、所有电缆必须采用五芯电缆,导线采用绝缘铜导线。

2、从建设方配电室至配电房采用埋地电缆,配电房至施工现场采用架空敷设,电杆间距25m ~30m ,架空高度大于5m 。

3、电缆垂直敷设的位置利用在建工程垂直孔洞,并在靠近用电负荷中心设置分配电箱或开关箱。固定点每层楼不得少于一处。在建筑屋内电缆水平敷设沿墙或门口固定。

4、紧电缆用的铁丝或钢丝绳应能承受全部拉力,与电缆线连接必须牢固。紧线时导线下方不得站人。终端紧线时反方向应设置临时拉线。

5、电缆干线采用埋地或架空敷设,严禁沿地面明敷设,并应避免机械损伤和介质腐蚀。

6、电缆在室外直接埋地敷设时,必须按电缆埋设图敷设,并应砌砖槽防护,

埋设深度不得小于0.7m.

7、电缆的上下各均匀铺设不小于5cm 厚的细砂,上盖电缆盖板或红机砖作为电缆的保护层。

8、地面上应有埋设电缆的标志,并应有专人负责管理。不得将物料堆放在电缆埋设的上方。

9、有接头的电缆不准埋在地下,接头处应露出地面,并配有电缆接线盒。电缆接线盒应防雨、防尘、防机械损伤,并远离易燃、易爆、易腐蚀场所。

10、电缆穿越建筑物、构筑物、道路、易受机械损伤的场所及引出地面从2m 高度至地下0.2m 处,必须加设防护套管。

11、电缆线路与其附近热力管道的平行间距不得小于2m ,交叉间距不得小于1m 。

六、现场勘探及线路走向

现场主是由甲方提供的变压器接入现场所修的配电房,提供电压为380/V,总容量为500kW, 根据施工现场建筑特点和临时用电设备布设,按现场施工临时用电布置图,施工临时用电从配电房用电缆架空引出(或埋地), 引至现场一级配电柜(施工配电房)处, 再由一级配电柜分出塔吊、钢筋加工车间、木工车间、其他小型设备施工用电、生活及照明用电专用。

七、级电箱位置及布线原则:

(1)塔吊配电箱设在基础边,便于电源进出线。

(2)钢筋加工配电箱设在钢筋加工棚处,采用埋地敷线,以便材料进场。 (3)振捣器配电箱应布置在使用地点附近(即流动电箱)。

(4)砂浆机、灰机的配电箱设在砂场及灰池附近,导线采用架空敷设。 (5)电焊机为可移动设备,采用回路供电,导线采用橡皮套软电缆。 (6)分配电箱距固定式用电设备距离均不超过3米,距交流弧焊机距离不大于5米。

第三章 施工用电计算

一、施工用电计算说明:

本工程在人工挖孔桩施工完毕后,大部分空压机、潜水泵需出场,施工用电配电容量不考虑空压机与潜水泵的施工用电。本计算只考虑用电主干线。

二、施工用电总容量计算:

本工程孔桩施工完毕后,大部分空压机、潜水泵和打夯机需出场,配电容量不考虑空压机、潜水泵、打夯机的施工用电。

1、电动机功率:

∑P =塔吊电动机功率+井架电动机功率+钢筋加工机械电动机功率

+砂浆机电动机功率=50+25+72.52+15=162.5(KW)

2、电焊机容量

∑P 1=93.6(KWA)

3、动力用电容量:

P动= K1×∑P 1÷cos φ+ K2×∑P 2

=0.6×509.4÷0.7+0.6×93.6=361.8(KVA) 4、照明用电容量:

考虑本工程工期紧,夜间施工较多,取动力用电容量的15%。 P照=0.15 P动=0.15×361.8=54.27(KVA) 5、用电总容量为:

∑P 总= P动+ P照=361.8+54.27=416.07(KVA)

三、所需变压器容量:

W=K×∑P 总÷ cosφ=1.05×416.07÷0.75=582.498(KVA) 式中说明:K=功率损失系数。

业主提供的电源变压器容量为600KVA ,能满足施工最大用电高峰要求。 变压器到配电房采用150mm 2绝缘铝芯橡皮导线。

四、用电管理措施:

为此,采取用电分配控制措施,使用主要的大功率用电设备分时间段错开使用,避免用电出现最高峰以导致变压器受损。 五、按工作电流选择配电导线截面:(主线)

1、Ⅰ路工作电流: 1.1动力部分:

I动力 =K1×∑P ÷(√3×V ×cos φ)

={0.6×[215.8+(0.6×46.8)]×1000}÷[√3×380×0.75] =296.43(A)

1.2照明部分:

I照明 =0.15×I 动力=0.15×296.43=44.46(A) 1.3工作电流:

I工作电流= I动力+ I照明=296.43+44.46=340.89(A) 1.4导线截面选择:

查表选用150mm 2的绝缘铝芯橡皮导线。 2、Ⅱ路工作电流: 2.1动力部分:

IⅡ路动力 =K1×∑P ÷(√3×V ×cos φ)

={0.6×[226.8+(0.6×46.8)]×1000}÷[√3×380×0.75] =309.81(A)

2.2照明部分:

IⅡ路照明 =0.15×I Ⅱ路动力=0.15×309.81=46.47(A) 2.3工作电流:

IⅡ路工作电流= IⅡ路动力+ IⅡ路照明=309.81+46.47=356.28(A) 2.4导线截面选择:

查表选用150mm 绝缘铝芯橡皮导线。

2

第四章 安全用电技术措施和电气防火措施

一、技术措施:

1、施工现场配有专业电工一名负责施工现场临时用电(持证上岗)。 2、配电房:

2.1配电房门向外开,并上锁,严禁无关人员进入,不准堆放任何杂物,配置两台干粉灭火器。

2.2供电系统采用三相五线制,漏电保护器和空气开关的选择执行国家标准。

2.3配电盘正面的操作通道宽不小于1.5m, 背面的维护通道宽不小于0.8m 。 2.4配电盘应设短路、过负荷保护装置和漏电保护器,配电盘上的各配电线路排列整齐,标记齐全清楚,并标明用途。

2.5配电盘和配电线路维修时,应悬挂停电标志牌,停、送电必须由持证专业电工负责。送电时必须先合隔离开关,后合空气开关或漏电断路器;停电操作顺序相反。

2.6总配电箱中漏电保护器的额定漏电动作电流应大于150mA ,额定漏电动作时间应大于0.2S ,但其额定漏电动作电流与额定漏电动作时间的乘积不应大于30mA ·s 。

3、配电线路:

引入和引出电缆干线采用埋地敷设,埋地深度为0.7m ,埋置于环境干燥且无介质腐蚀。

室内配线采用绝缘导线,用塑料卡敷设,距地面高度不得小于2.5m, 铜线截面不得小于1.5mm 2。

4、配电箱及开关箱:

4.1配电系统设置室内总配电屏和室外总配电箱、分配电箱,实行分级配电。室内总配电屏动力和照明线路分路设置,开关箱由末级分配电箱配电。

4.2配电箱、开关箱设在干燥、通风及常温场所,不得有灌木和杂草, 其周围应有足够二人同时工作的空间和通道,并不得堆放任何防碍操作、维修的物品。

4.3配电箱、开关箱应装设端正、牢固,移动式配电箱、开关箱装设在坚固的支架上,配电箱、开关箱内的电器必须可靠完好,不准使用破损、不合格的电

器。

4.4分配电箱应装设总隔离开关和分路隔离开关以及总熔断器和分路熔断器。总开关电器的额定值、动作整定值应与分路开关电器的额定值、动作整定值相适应。

4.5每台用电设备设置各自专用的开关箱,实行“一机一闸”制,严禁同一个开关电器直接控制二台及二台以上的用电设备。

4.6开关箱中必须装设漏电保护器,漏电保护器装设在负荷线的首端处。

4.7漏电保护电器应装设在配电箱电源隔离开关的负荷侧,漏电保护电器的选择应符合国标GB6829-86《漏电电流动作保护器(剩余电流动作保护器)》的要求,开关箱内的漏电保护电器其额定漏电动作电流不大于30mA ,额定漏电动作时间不大于0.1S ,

4.8配电箱、开关箱中导线的进线口和出线口应设在箱体的下底面,严禁设在箱体的上顶面、侧面、后面或箱门处,导线束不得与箱体进出口直接接触。移动式配电箱、开关箱的进、出线必须采用橡皮绝缘电缆。

4.9所有配电箱、开关箱应每月检查一次,检查、维修时必须由专业电工按规定穿、戴绝缘鞋、手套,必须使用电工绝缘工具。

5、电动建筑机械和手持电动工具:

5.1施工现场一切电动建筑机械和手持电动工具的选购、使用、检查和维修必须遵守下列规定:

5.1.1选购的电动建筑机械、手持电动工具和用电安全装置,应符合相应的国家标准、专业标准和安全技术规程,并且有产品合格证和使用说明书。

5.1.2建立和执行专人专机负责制,并定期检查和维修保养。

5.1.3保护零线的电气连接和漏电保护器按规范设置,保护接地线严禁作为零线使用。

5.1.4楼层上每隔两层设置施工配电箱,配电箱之间配电电缆采用橡套电缆穿PVC 管明配,施工用具振动器、电焊机等电源线采用橡套电缆,保护接地可靠,漏电保护开关动作灵敏,不能带电移动施工用具,特殊设备振动器使用过程中移动时不允许强行拖拉电源线,必须另外有人员帮助移动电缆。

5.1.5在施工现场的工具和材料不允许堆放电线电缆上,现场人员不允许在

电线电缆上踩踏。

5.1.6现场施工用水管要和配电箱及电线电缆保持一定的距离,防止水飞溅到配电设备和用电设备上;施工完毕后用电设备进线端必须断电,用电设备和配电箱要经常覆盖,防止下雨淋湿。

5.2夯土机械:

5.2.1夯土机械开关箱中的漏电保护器额定漏电动作电流不得大于30mA ,额定漏电动作时间不大于0.1S ;

5.2.2夯土机械PE 线的连接点不得小于2处;

5.2.3夯土机械的负荷采用耐气候型橡皮护套铜芯软电缆;

5.2.4使用夯土机械按规定穿戴绝缘用品,使用过程派专人调整电缆,电缆长度不大于50m 。电缆严禁缠绕、扭结和被夯土机械跨越;

5.2.5夯土机械的操作扶手必须绝缘。

5.3起重机械(塔吊、物料提升机):

5.3.1塔吊的电气设备符合《塔式起重机安全规程》GB5144的要求;

5.3.2塔吊的电气设备所连接PE 线必须同时做重复接地,重复接地和防雷接地可共用同一接地体,但接地电阻应符合重复接地电阻值的要求;

5.3.3物料提升机的上下极限位置设置限位开关;

5.3.4每日工作前必须对行程开关、限位开关、紧急停止开关、驱动机械和制动器等进行空载检查,正常后方可使用。检查时必须有防坠落措施。

5.4焊接机械:

5.4.1电焊机放置在防雨、干燥和通风良好的地方;焊接现场不得有易燃、易爆物品;

5.4.2交流弧焊机变压器的一次侧电源线长度不大于5m ,其电源进线必须设置防护罩。

5.4.3电焊机械开关箱中的漏电保护器额定漏电动作电流不应大于30mA ,额定漏电动作时间不应大于0.1S 。

5.4.4电焊机械的二次线应采用防水橡皮护套铜芯软电缆,电缆的长度不应大于30m ,不得采用金属构件或结构钢筋代替二次线的地线。

5.4.5使用电焊机械焊接时必须穿戴防护用品,严禁露天冒雨从事电焊作

业。

6、手持式电动工具:

6.1空气温度小于75%的一般场所可先用Ⅰ类或Ⅱ类手持式电动工具,其金属外壳与PE 线的连接点不得小于2处;除塑料外壳Ⅱ类工具外,相关开关箱中漏电保护器的额定漏电动作电流不应大于15mA ,额定漏电动作时间不应大于0.1S ,其负荷线插头应具备专用的保护触头。所用插座和插头在结构上应保护一致,避免导电触头和保护触头混用。

6.2在潮湿场所或金属构架上操作时,必须选用Ⅱ类或由安全隔离变压器供电的Ⅲ类手持式电动工具。金属外壳Ⅱ类手持式电动工具使用时,必须符合6.1条要求;其开关箱和控制箱应设置在作业场所外面。在潮湿场所或金属构架上严禁使用Ⅰ类手持式电动工具。

6.3狭窄场所必须选用由安全隔离变压器供电的Ⅲ类手持式电动工具,其开关箱和安全隔离变压器均应设置在狭窄场所外面,并连接PE 线。漏电保护器的额定漏电动作电流不应大于15mA ,额定漏电动作时间不应大于0.1S 。

6.4手持式电动工具的负荷线应采用耐气候型的橡皮护套铜芯软电缆,并不得有接头。

6.5手持式电动工具的外壳、手柄、插头、开关、负荷线等必须完好无损,使用前必须做绝缘检查和空载检查,在绝缘合格、空载运转正常后方可使用。

6.6使用手持式电动工具时,必须按规定穿、戴绝缘防护用品。

7、照明:

7.1照明器具和器材的质量均应符合有关标准、规范的规定,不得使用绝缘老化或破损的器具和器材。

7.2照明系统的每一个单相回路上,灯具和插座数量不得超过25个,并应装设熔断电流为15A 及15A 以下的熔断器保护。

7.3照明灯具金属外壳必须作保护接零,室外灯具距地面不得低于3m ,室内灯具不得低于2.4m 。

7.4电器、灯具的相线必须经开关控制,不得将相线直接引入灯具。

8、接地和防雷:

8.1施工现场采用TN -S接零保护系统。电气设备的金属外壳必须与专用的

保护零线连接。

8.2施工现场严禁利用大地作为相线或零线,保护零线不得装设开关或熔断器。

8.3保护零线单独设置,不作它用。重复接地应与保护零线相连接,与电气设备相连接的保护零线应为截面不小于2.5mm 的绝缘多股铜线。

8.4正常情况下,下列电气设备不带电的外露导电部分应接地:

8.4.1电机、电器、照明器具、手持电动工具的金属外壳。

8.4.2电气设备传动装置的金属部件。

8.4.3配电屏和控制屏的金属框架。

8.4.4室内外配电装置的金属框架及靠近带电部分的金属围栏和金属门。

8.5塔吊利用桩基作为重复接地,接地可靠, 接地电阻小于1Ω。

9、工地的一切用电设备必须由电工接线和管理,不得擅自架设和装电路,电工必须持证上岗,严禁违章操作。

10、电工在接线、电气设备安装时,应按照施工设计和有关电气安全技术规程进行作业,应正确使用绝缘防护用品和经定期检查校验的绝缘检验工具。电气操作人员严格执行电工操作规程。

11、电缆架空敷设时,应沿墙壁或电杆设置,并和绝缘子固定,严禁用金属裸线作绑线,室外架空高度不小于3M ,室内不小于2.5M 。水平沿墙敷放或门口固定最低点不得小于1.8M 。

12、电工人员严禁带电操作,线路上禁止带负荷接线,正确使用电工器具。

13、电气设备的金属外壳必须做接地、接零保护。

14、电气设备所用保险丝,禁止用其它金属丝代替,并且需与设备容量相匹配。凡移动式照明,必须采用安全电压。

15、施工现场临时用电施工,必须执行施工组织设计和安全操作规程。

16、开机前认真检查开关箱内的控制开关设备是否齐全有效,漏电保护器是否可靠,方能使用。严禁赤手触摸一切带电绝缘导线。

17、下班后1小时必须把总电制关好并把电箱门锁上。

18、电工必须定期检查所有漏电开关是否正常,并认真登记安全生产检查记录。 2

19、开关箱距操作者的水平距离不超过3米,按钮开关不能安装在交流接触器一侧。

20、开关箱内禁止放任何杂物,箱不能堆放沙子、水泥、白灰、水泥袋等,且灌木、杂草要清除干净。

21、开关箱安装距地面高度为1.3M-1.5M ,且安装牢固,要具有防尘、防雨功能。

22、开关箱必须完整无缺,并配上锁,锁匙由专人保管。

23、开关箱必须有当心触电的标志。

24、三级漏电保护开关的额定漏电动作电流应不大于30mA ,额定漏电动作时间应小于0.1S 。

25、其余规定参照《施工现场临时用电安全技术规范》JGJ46-2005。

二、防火措施

1、合理配置用电系统的短路、过载、漏电保护电器;

2、确保PE 线连接点的电气连接可靠;

3、在电气设备和线路周围不堆放并清除易燃易爆物和腐蚀介质,并作阻燃隔离防护;

4、不在电气设备周围使用火源,特别在配电室、配电箱等场所严禁烟火;

5、在电气设备相对集中场(配电室、钢筋加工车间、木工车间等)配置干砂、干粉灭火器,禁止使用灭火剂灭火;

6、建立电气防火责任制,加强电气防火重点场所烟火管制,并设置禁止烟火标志;

7、建立电气防火教育制度,定期进行电气防火知识宣传教育,提高现场各工种和人员电气防火意识和电气防火知识水平;

8、建立电气防火检查制度,发现问题,及时处理,不留任何隐患;

9、电焊作业时须配置灭火器,并派专人监护,作业完毕,留有充分的时间观察,确认无引火点后,方可离去;

10、施工现场焊、割作业前执行“动火证制度”,并切实做到用火有措施,灭火有准备;

第五章 施工现场用电平面布置图

见附图

第六章 施工现场临时用电管理制度

一、电气维护制度

1、只准全部(操作范围内)停电工作、部分停电工作,不准进行不停电工作。维修工作要严格执行电气安全操作规程。

2、不准私自维修不了解内部原理的设备和装置。不准私自维修厂家禁修的安全保护装置。不准私自超越指定范围进行维修作业。不准从事超越自身技术水平且无指导人员在场的电气维修作业。

3、不准在本单位不能控制的线路及设备上工作。

4、不准随意变更维修方案而使隐患扩大。

5、不准酒后或有过激行为之后进行维修作业。

6、对施工现场所属的各类电动机,每年必须清扫、注油或检修一次。对变压器、电焊机,每半年必须进行清扫或检修一次。对一般低压电器、开关等,每半年检修一次。

二、工作监护制度

1、在带电设备附近工作时必须设人监护。

2、在狭窄及潮湿场所从事用电作业时必须设专人监护。

3、登高用电作业时必须设专人监护。

4、监护人员应时刻注意工作人员的活动范围,督促其正确使用工具,并与带电设备保持客观存在全距离。发现违反电气安全规程的作法应及时纠正。

5、监护人员的安全知识及操作技术水平不得低于操作人。

6、监护人员在执行监护工作时,应根据被监护工作情况携带或使用基本安全用具或辅助安全用具,不得兼做其他工作。

三、安全用电技术交底制度

1、进行临时用电工程的安全技术交底,必须分部分项且按进度进行。不准一次性完成全部工程交底工作。

2、设有监护人的场所,必须在作业前对全体人员进行技术交底。

3、对电气设备的试验、检测、调试前、检修前及检修后的通电试验前,必须进行技术交底。

4、支电气设备的业期维修前、检查后的整改前,必须进行技术交底。

5、交底项目必须齐全,包括使用的劳动保护用品及工具,有关法规内容,有关安全操作规程内容和保证工程质量的要求,以及作业人员活动范围和注意事项等。

6、填写交底记录要层次清晰,交底人、被交底人及交底负责人必须分别签字,并准确注明交底时间。

四、安全检测制度

1、测试工作接地电阻和防雷接地电阻值,必须每年在雨季前进行。

2、测试重复接地电阻值必须每季至少进行一次。

3、更换和大修设备或每移动一次设备,应测试一次电阻值。测试接地电阻值工作前必须切断电源,断开设备接地端。操作时不得少于两人,禁止在雷雨时及降雨后测试。

4、必须对漏电保护器进行一次主要参数的检测,不符合铭牌值范围时应立即更换或维修。

5、对电气设备及线路、施工机械电动机的绝缘电阻值,每年至少检测两次。摇测绝缘电阻值,必须使用与被测设备、设施绝缘等相适应的(按安全规程执行)绝缘摇表。

6、检测绝缘电阻前必须切断电源,至少两人操作。禁止在雷雨时摇测大型设备和线路的绝缘电阻值。检测大型感性和容性设备前后,必须按规定方法放电。

五、电工及用电人员的操作制度

1、禁止使用或安装木质配电箱、开关箱、移动箱。电动施工机械必须实行

“一机一闸一漏一箱”。且开关箱与所控固定机械之间的距离不得大于5M 。

2、严禁以取下(给上)熔断器方式对线路停(送)电。严禁维修时约时送电,严禁以三相电源插头代替负荷开关启动(停止)电动机运行。严禁使用220V 电压行灯。

3、严禁频繁按动漏电保护器和私拆漏电保护器。

4、严禁长时间超铭牌额定值运行电气设备。

5、严禁在同一配电系统中一部分设备作保护接零,另一部分设备作保护接地。

6、严禁直接使用刀闸启动(停止)4KW 以上电动设备。严禁直接在刀闸上或熔断器上挂接负荷线。

第七章 应急措施

一、触电事故应急措施:

1、现场人员应当机立断地脱离电源,尽可能的立即切断电源(关闭电路),亦可用现场得到的绝缘材料等器材使触电人员脱离带电体。

2、将伤员立即脱离危险地方,组织人员进行抢救。

3、若发现触电者呼吸或呼吸心跳均停止,则将伤员仰卧在平地上或平板上立即进行人员呼吸或同时进行体外心脏按压。

4、立即拨打120向当地急救中心取得联系(医院在附近的直接送往医院),应详细说明事故地点、严重程度、本部门的联系电话,并派人到路口接应。

5、立即向公司应急抢救领导小组汇报事故发生情况并寻求支持。

6、维护现场秩序,严密保护事故现场。

二、应急物资

常备药品:消毒用品、急救物品(绷带、无菌敷料)及各种常用小夹板、担架、止血袋、氧气袋。

三、注意事项

1、在末脱离电源时,切不可用手去拉触电者。

2、事故发生时应组织人员进行全力抢救,视情况拨打120急救和马上通知有关负责人。

3、注意保护好事故现场,便于调查分析事故原因。

4、心肺复苏抢救措施要坚持不断的进行(包括送医院的途中)不能随便放弃。

第八章 施工现场用电管理机构设置

一、施工现场用电安全领导小组:

成立以项目经理为首的“惠水县高镇安置小区工程项目安全领导小组”,组织机构如下:

二、管理措施:

1、用电安全检查制度:

严格监督检查,消除事故隐患。用电安全领导小组每周定期对项目进行检查;专职电工、机电员和安全员坚持每日安全巡视。对检查发现的事故隐患,定人、定时间、定措施进行整改,不留事故隐患。机械设备、施工用电、防护设施等要经验收合格后才能投入使用。每次检查后,由安全员作好记录,归入档案。

2、班前安全活动:

开工前,必须由安全员及班组长对工人进行安全技术交底,并履行签字手续。活动后由安全员作安全教育活动记录。

3、安全教育:

3.1日常教育:广泛开展安全生产的宣传教育,在工人进场和施工全过程中,对全体施工人员进行安全思想教育、施工安全知识教育,使施工人员真正认识到

安全生产的重要性和必要性,提高施工人员的安全意识和安全生产素质,为安全生产打好基础。

3.2安全纪律教育:使施工人员了解安全生产规章制度、安全生产责任制、安全生产劳动纪律、安全生产奖惩条例,增强全员的安全生产法制意识,使其能自觉遵守各项安全生产法令和规章制度。

3.3安全技术教育:对各岗位操作人员进行本岗安全生产知识和技术教育;对特殊岗位操作人员进行培训,考核合格后持证上岗。

3.4班前安全交底:班前对工人进行简洁而明确的安全、技术交底和动员,并交代好操作事项,班后要对当日的安全生产状况进行讲评,改进措施,总结经验。

3.5 操作工艺交底:由项目技术主管保证工程的操作工艺无安全缺陷,并负责将操作工艺向具体施工人员交底,交底以书面形式进行,以使操作人员对操作的危险性和防卫措施有充分的了解。

三、工地消防管理:

1、成立以项目经理为组长的现场消防小组,负责消防管理。

2、消防小组人员定期进行消防检查。

3、保证消防道路畅通,有明显防火标志和防水制度牌,消防设施器具,足够合格有效,消防器材不得随便动用。

4、施工材料按防火安全要求存放,保管易燃、易爆材料专库储存,库房按防火要求和火等级搭建,易燃、易爆剧毒物品单独存放严格控制。

5、特殊工种持证上岗,电气焊工明火作业要有用火证,派专人负责并配灭火器,禁止违章作业。

6、做好成品保护,防止破坏行为,发生火灾及进报警。

7、冬季施工使用电热器,须符合安全规范,并经消防负责人同意,冬季施工用保温材料,不得采用可燃材料。

8、施工中使用化学易燃物器时,禁止交叉作业和作业场所分装,调料。


相关内容

  • 江苏省文明工地安全管理资料目录
  • 安全管理资料部分 1.中标通知书 2.建设工程施工合同 3.安全报监书 4.建筑工程施工许可证 5.建设工程规划许可证 6.企业法人营业执照复印件 7.企业资质证书复印件 8.安全生产许可证复印件 9.安全生产十项技术措施 10.安全生产六大纪律 11.起重吊装"十不吊"规定 1 ...

  • 危险作业审批和电气临时线审批制度
  • 危险作业审批和电气临时线审批制度 1.目的 为了规范安全作业行为,减少或杜绝作业环节发生安全事故的可能性,特制定本制度. 2.范围 适用于公司各部门的动火作业.受限空间内作业.临时用电作业.高处作业等危险性较高的作业活动的安全管理. 3.职责 3.1安全员负责各危险作业环节的综合安全监督管理. 3. ...

  • 化工企业安全作业许可证管理制度
  • 内蒙古皓海化工有限公司 安全作业许可证管理制度 1.目的 为规范危险性作业管理,预防事故发生,保护员工生命和财产安全,特制定本制度. 2.范围 公司生产区域内动火作业.进入受限空间作业.临时用电作业.高处作业.吊装作业.动土作业.断路作业.设备检修作业.高温作业.抽堵盲板作业等危险性作业. 3.职责 ...

  • 危险作业管理规定
  • 文件 编号:EOG/YP 3 35 016-2015 危险作业管理规定 (D版) 发布日期:2015年10月09日 实施日期:2015年10月09日 1 目的 为加强生产过程中的危险作业审批和管理,提高危险作业的安全性和可靠性. 2 适用范围 本制度适用于玉柴马石油润滑油公司各部门.工程项目承包单位 ...

  • 八大安全作业管理制度
  • 安全作业"八大制度" 东营市银丰进出口有限公司 安全作业制度目录 1.动火作业安全管理制度 2.进入受限空间作业安全管理制度 3.临时用电安全管理制度 4.高处作业安全管理制度 5.吊装作业安全管理制度 6.设备安全检修制度 7.焊接作业安全管理制度 8.高温作业安全管理制度 动 ...

  • 九大作业票证及安全规程
  • ZhangJiaGang JiangNan Powder Coating Co.,Ltd. 张家港江南粉末涂料有限公司 江南粉末涂料有限公司 编 日 九 大 作 业 票 证 制:顾 湘 洪 期:2015年9月1日 张家港江南粉末涂料有限公司江南粉末涂料有限公司 九大作业票证目录 ZhangJiaGa ...

  • 巨化公司八大作业票管理制度(修订中)
  • 安徽巨成精细化工有限公司 八大作业票证管理 安 全 规 程 安徽巨成精细化工有限公司 八大作业票证安全规程目录 一.八大作业票证安全管理制度 第一章总则 动火作业安全规程 二.高处作业安全规程 三.设备检修作业安全规程 四.吊装作业安全规程 五.盲板抽堵作业安全规程 六.设备内检修作业安全规程 七. ...

  • 施工现场安全检查通知书
  • 施工现场安全检查通知书建 设 单 位 提 供 的 资 料 监 理 单 位 提 供 的 资 料[1**********] 11 12 13 14 15 16 17 18 19 20建设工程规划许可证.施工许可证地下管线交底资料总包合同及专业分包合同.监理合同与施工单位签订的安全生产协议书工程款拨付票据 ...

  • 123安全旁站监理实施方案
  • 长沙县菖马公路(青山铺镇段)提质 改造工程 安 全 监 理 旁 站 方 案 编制: 审批: 湖南和天工程项目管理有限公司 长沙县菖马公路(青山铺镇段)提质改造工程监理处 二○一六年八月 目 录 一.旁站监理实施依据 二.安全旁站监理的范围 三.安全监理措施 四.安全监理的程序和主要内容 五.安全监理 ...

  • 建设工程施工现场临时设施管理通用办法
  • 建设工程施工现场临时设施管理通用办法 第一章 总 则 第一条 为了强化施工现场临时设施的管理,本着科学合理.安全实用.符合标准.节约开支的原则,杜绝私建.乱建.超标建设现象,以达到临时设施管理的规范化.标准化.科学化的目的,特制定本办法. 第二条 本管理办法依据<中华人民共和国建筑法>. ...